4/20 2015-03-06 CE1G3333xx Siemens Building Technologies
Operating action:
Where? What?
DIP switch block,
switches no. 1 and 2
1 2
Heating and cooling in sequence
Two-stage heating
Single-stage cooling
Single-stage heating
Control mode and integral action time:
DIP switch block,
switches no. 3 and 4
3 4
P-mode
PI mode, integral action time = 120 s
(MEDIUM)
PI mode, integral action time = 240 s
(SLOW)
PI mode, integral action time = 60 s (FAST)
Test mode:
DIP switch block,
switch no. 5
5
Test mode
Normal operation
Outside temperature compensation:
DIP switch block,
switch no. 6
6
HIGH
LOW
P-band Y1
Potentiometer no. 5
Potentiometer setting should correspond to the re-
quired range of the controller’s output signal
P-band Y2
Potentiometer no. 4 Potentiometer setting should correspond to the re-
quired range of the controller’s output signal
Setpoint increase / decrease:
Slider 3
Setpoint or limit value:
Temperature
setting slider 5
Adjust after commissioning
Indication of operating state
The red LED indicates the controller’s operating state:
LED lit: Mains voltage present
LED flashes: In test mode
The LED is also visible when the cover is fitted.
Commissioning
When used as a controller
1. Remove housing cover.
2. Lift flexible plastic cover so that you can access the
setting elements.
3. Make the settings:
Operating mode (switches no. 1 and 2)
Control mode and (with PI mode) integral action
time (switches no. 3 and 4)
Test mode: Switch no. 5 =
Outside temperature compensation (when using an
outside sensor)
P-band Y1 (potentiometer 5) and Y2 (potentiome-
ter 4)
Setpoint increase or decrease (slider 3)
4. Replace flexible plastic cover.
5. Switch power on. LED for the operating state must
flash (test mode).
6. First, set temperature setting slider to the minimum
value, then to the maximum value: Actuating device(s)
must travel to the minimum or maximum position.
If response is wrong, refer to “Troubleshooting”
7. Switch power off.
8. Switch controller to normal operation (set switch no. 5
to
).
9. Switch power on. LED for the operating state must
light up (normal operation).
10. If used, activate auxiliary functions (setpoint change-
over, load-dependent switching contact, etc.).
11. If a remote setting unit is used, set the controller’s
temperature setting slider to EXT.
12. First, set temperature setting slider to the minimum
value, then to the maximum value: Observe the con-
trol. The response may neither be too fast nor too
slow.
If response is wrong, refer to “Troubleshoot-
ing”
13. Adjust the setpoint with the temperature setting slider.
14. Replace housing cover.
As a limiter
1. Switch on the temperature control.
2. Remove housing cover (limiter).
3. Lift flexible plastic cover so that you can access the
setting elements.
4. Choose operating action according to the following
table:
Controller: Limiter:
Operat-
ing mode
Switches
1 and 2
Limita-
tion
Operating
mode
Switches
1 and 2
Heating
Min. Heating
Heating
Max. Cooling
5. Make the following additional settings:
Control mode: P (switch no. 3 = , switch no. 4 =
)
Test mode: Switch no. 5 =
P-band Y1 on approx. 25 K
6. Replace housing cover.
7. Switch power on. LED for the operating state must
flash (test mode).
8. Check function depending on the type of limitation:
With minimum limita-
tion:
With maximum limitation
Set temperature setting
slider to the maximum
value:
Controller must increase
the temperature (heating
valve must open, cooling
valve must close)
Set temperature setting
slider to the minimum val-
ue:
Controller must reduce the
temperature (heating valve
must close, cooling valve
must open)
If response is wrong, refer to “Troubleshooting”
9. Switch power off.
10. Switch limiter to normal operation (set switch no. 5 to
)
11. Adjust the limit temperature.
12. Replace housing cover.
4

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens RLE162 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info