Siemens Building Technologies CE1G3332xx 2015-03-06 3/20
In the supply air duct downstream from the supply air
fan if fan is installed after the last air handling unit,
otherwise
In the supply air duct downstream from the last air
handling unit in a distance of 0.5 m
As a minimum supply air temperature limiter:
In the supply air duct as close as possible to the air dis-
charge into the room
As a dewpoint controller:
Immediately downstream from the droplet separator of
the air washer
Mounting
Procedure:
1. First mount the flange. For drilling holes, refer to “Di-
mensions”.
2. Bend flexible sensing element manually (never use a
tool) so that – when mounted – it stretches diagonally
across the air duct .
Note! The flexible sensing element may not touch the
duct wall: The minimum clearance is 50 mm and the
smallest permissible bending radius 10 mm
3332Z03
3. Fit mounting flange.
4. Slide controller on mounting flange and snap it on.
Electrical installation
Ensure that the local regulations for electrical installa-
tions are complied with
The connecting terminals are located under the flexible
plastic cover
Make wiring according to the plant documentation. If not
available, use the connection diagrams contained in
these Installation Instructions
Observe the permissible cable lengths
Switch on power only when commissioning the controller
External preliminary protection with max. C 10 A circuit
breaker is required in all cases
Settings
1
6
23 5
3332P02
4
1 LED for test mode / normal operation
2 DIP switch block
3 Setting slider for setpoint increase or decrease
4 Setting potentiometer for the relay Q13–Q14
5 Setting potentiometer for the P-band
5 Temperature setting slider for setpoint or limit value
Operating action:
Where? What?
DIP switch block,
switches no. 1 and 2
1 2
Heating and cooling in sequence
Two-stage heating
Single-stage cooling
Single-stage heating
Control mode and integral action time:
DIP switch block,
switches no. 3 and 4
3 4
P-mode
PI mode, integral action time = 600 s
(SLOW)
PI mode, integral action time = 120 s
(FAST)
PI mode, integral action time = 180 s
(MEDIUM)
Test mode:
DIP switch block,
switch no. 5
5
Test mode
Normal operation
Outside temperature compensation:
DIP switch block,
switch no. 6
6
HIGH
LOW
Switching contact Q13–Q14:
Potentiometer 4 Potentiometer setting should correspond to the re-
quired switching point of output relay Q13–Q14
P-band Y1 (not adjustable for Y2):
Potentiometer 5 Potentiometer setting should correspond to the re-
quired range of the controller’s output signal
Setpoint increase / decrease:
Slider 3
Setpoint or limit value (supply or extract air temp.):
Temperature setting
slider 6
Adjust after commissioning
Indication of operating state
The red LED indicates the controller’s operating state:
LED lit: Mains voltage present
LED flashes: In test mode
The LED is also visible when the cover is fitted.
Commissioning
When used as a controller
1. Remove housing cover.
2. Lift flexible plastic cover so that you can access the
setting elements.
3. Make the settings:
Operating action (DIP switches 1 and 2)
Control mode and (with PI mode) integral action
time (DIP switches 3 and 4)
3

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens RLM162 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info