Siemens Building Technologies CE2N2462E / 09.12.1998
Landis & Staefa Division 3/8
All electric or electro-hydraulic actuators for three-position control made by Landis &
Staefa can be used:
Operating voltage AC 24...230 V
Maximum running time 6 minutes (recommended: 2 to 3 minutes)
All electro-thermal actuators for two-position control:
Operating voltage AC 24...230 V
Running time 8 to 16 minutes
When ordering, please give type reference according to "Type summary". If a controller
with a weekly time switch is required, it must be ordered without the time switch, that is,
RVP200.0
or
RVP210.0
, plus the required time switch (
AUZ3.7
or
AUD3
). Detectors,
room unit, actuator and valve must be ordered as separate items.
Weather-compensated control: the setpoint of the flow or boiler temperature is con-
tinuously shifted in function of the outside temperature (via the outside detector). As-
signment of the flow temperature to the actual outside temperature is made via the
heating curve. Its slope is adjustable
Weather-compensated control with room temperature influence: the setpoint of the
flow or boiler temperature is continuously shifted in function of the outside tempera-
ture (via the outside detector) and, in addition, in function of the setpoint / actual value
deviation of the room temperature.
Room temperature authority = 199 % (adjustable, guide value is 50 %)
Room temperature-compensated control: the setpoint of the flow or boiler tempera-
ture is continuously shifted in function of the setpoint / actual value deviation of the
room temperature
With both types of weather-compensated control, the composite outside temperature is
used as the compensating variable. It is generated from the actual and the attenuated
outside temperature. Compared to the actual outside temperature it is ssignificantly at-
tenuated and delayed.
20 10
0
-10 -20 -30
90
80
70
60
50
40
30
4
3,5 3 2,75 2,5 2,25
2
1,75
1,5
1,25
1
0,75
0,5
0,25
100
2462D01
T
V
T
A
110
20
T
A
Outside temperature [°C]
T
V
Flow temperature[°C]
Three-position control: the flow temperature is controlled continuously with no offset
via a seat or slipper valve driven by an electric or electro-hydraulic actuator
Two-position control: the flow temperature is controlled via a seat or slipper valve
driven by an electro-thermal actuator. The switching differential is 1 K
Maximum limitation of the flow temperature can be provided in the range 8100 °C.
This function can be deactivated.
The boiler temperature is controlled by a single-stage burner which is switched on and
off. The burner's minimum on time is four minutes. The switching differential is adjust-
able in the range 120 K.
Maximum limitation of the boiler temperature can be provided in the range 8100 °C.
This function can be deactivated.
If the boiler temperature falls below 5 °C, the burner will be switched on to maintain a
minimum boiler temperature.
When there is no demand for heat and during quick setback, the boiler will be switched off.
Suitable actuators
Ordering
Technical design
Compensating variables
Heating curve chart
Flow temperature control
Boiler temperature control
3

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln
1

Forum

siemens-rvp200

Suche zurücksetzen

  • Raumthermostat qaw70- Steht aus Auto
    Regler RVP200 steht auf Auto(Sonne-Mond) muß Override leuchten Eingereicht am 9-9-2021 15:48

    Antworten Frage melden

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens RVP200 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info