Building Technologies 74 319 0614 0 c 20.05.2008 4/26
- If it flashes, the detector wiring may be faulty
- If it is lit, the controller is overridden by a remote operation
facility (room unit or changeover switch). Set room unit to
operating mode
or open the external switch)
4. Set operating mode selector to
.
5. Set heating curve potentiometer
to 4 and setting knob
to +8 °C:
- Flow temperature must rise: burner on, valve open, heat-
ing circuit pump on (electro-thermal actuators respond with
a certain delay!)
- If not: check wiring of the detectors (flow/boiler, outside de-
tector), actuator/burner and heating circuit pump
6. Set operating mode selector to
.
7. Set heating curve to 0.25 and setting knob
to –8 °C:
- Burner must switch off (observe minimum running time of
4 minutes), valve must travel toward "colder", and heating
circuit pump must remain activated
- If not: check wiring of the detectors (flow/boiler, outside de-
tector), actuator/burner and heating circuit pump
Commissioning the remote operation facility
1. Set the controller's operating mode selector to one of the two
Auto positions
2. If a room unit is present: select operating mode
on the
room unit
- Check the "Override" LED on the controller: must be lit
- If not: check wiring of the room unit
3. If a changeover switch is present: close it (gives operating
mode
on the controller).
- Check the "Override" LED on the controller: must be lit.
- If not: check wiring of the changeover switch
Commissioning of D.h.w. heating
(only RVP211)
1. The D.h.w. temperature must be around 30 °C (check by
touching or use a measuring instrument).
2. Set the controller's operating mode selector to
.
3. Set setting knob
to 60 °C.
- D.h.w. temperature must rise: charging pump on or
changeover valve open
- If not: check wiring of the d.h.w. temperature detector and
the heating circuit pump, or the changeover valve
4. Set setting knob
to 10 °C (observe overrun time)
- Charging pump or changeover valve must switch off
- If not: check wiring of d.h.w. temperature detector
5. Reset setting knob
to 55 °C (factory-setting).
Setting elements
Refer to figure
3
on page 24
1 Opening for time switch
2 LED for "Override"
3 Operating mode selector
4 Setting knob for heating curve
5 Setting knob for setback
6 Setting knob for d.h.w. temperature (only RVP211)
7 Setting knob for normal room temperature
8 Coding switches
9 Setting potentiometer for authority of room temperature
and quick setback active / inactive
10 Setting potentiometer for max. limitation of flow or boiler
temperature
11 Setting potentiometer for ECO heating limit
12 Setting potentiometer for switching differential
Coding switches
Function Switch position on the left Symbol Symbol Switch position on the right
Type of regulating unit Control of a motorized valve
Control of a atmospheric or
forced draught burner
Type of control Three-position (modulating)
Two-position (on/off)
Frost protection Yes, frost protection
No, no frost protection
D.h.w. priority (only RVP211)
With priority (absolute). Underfloor
heating systems and boiler opera-
tions: always set to abs.!
No priority (parallel)
RVP211 with boiler temperature control:
Regulating unit for d.h.w. heating Changeover valve
Charging pump
Setting potentiometers
Settings must be determined during the planning phase.
If missing, the following guide values can be used.
Potentiometer Function Setting range Guide value Notes
Switching differential
with two-position
control
1…20 K Burner control: 6 K
Authority of room
temperature on flow
temperature control
0…100 % authority
Off = quick setback is
inactive
50 % (quick setback
is active)
Plants with no room unit: setting is inactive
Plants with no outside detector:
Setting 0…100 % = quick setback is active
Setting Off = quick setback is inactive
Heating limit for ECO
automatic energy
saver
–10…+8 K (referred to
the room temperature
set value)
–3 K (gives a heat-
ing limit of 17 °C at a
room temperature
set value of 20 °C)
Off = function disabled
Max. limitation of flow
or boiler temperature
10…100 °C Guide value for un-
derfloor and ceiling
heating systems:
55 °C max.
Off = function disabled
Settings on the controller
Seal the transparent cover, if required.
Heating curve diagram: Refer to figure
4
on page 24
T
A
Outside temperature [°C]
1. Set heating curve as specified in the planning documen-
tation or in compliance with local practices.
2. Reset setting knob
to 0 (factory-setting, corresponds
to 20 °C room temperature).
3. Leave setting knob
to –6 °C (factory-setting).
4. Set operating mode selector to one of the two
Auto posi-
tions.
5. Set time switch as indicated in the operating instructions.
T
V
Flow temperature [°C]
4

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens RVP201 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Siemens RVP201

Siemens RVP201 Bedienungsanleitung - Englisch - 46 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info