Siemens Heating controllers RVP201 and RVP211 CE1P2464en
Building Technologies 3 Technical design 12.12.2007
3.3.6 Control
Prerequisites for this type of control
Outside sensor connected
No room unit connected, or
Room authority set to 0 % or to Off if a room unit is connected
The compensating variable used for weather-compensated control is the composite
outside temperature. Assignment of the flow temperature setpoint to the compensating
variable is made via the selected heating curve. The room temperature is not taken into
consideration. This type of control is used primarily in plants or buildings where
several rooms are occupied at the same time
no room is suited as a reference room for the room temperature
Prerequisites for this type of control:
Room unit connected
No outside sensor connected, or
Room authority set to 100 % if an outside sensor is connected
If no outside sensor is connected, the setting potentiometer for the room authority is
inactive.
The compensating variable used for room temperature-compensated control is the
setpoint / actual value deviation of the room temperature. The room authority is gener-
ated based on this deviation. Also, an outside temperature of 0 °C is assumed and
taken into account when generating the setpoint.
When there is no temperature deviation in the room, the controller maintains the flow
temperature setpoint resulting from
0 °C outside temperature, and
the selected heating curve slope
Any room temperature deviation produces an instant parallel displacement of the se-
lected heating curve. The correlation between the extent of temperature deviation and
the degree of displacement is defined by the room authority, which is dependent on
the setpoint / actual value deviation of the room temperature
the selected heating curve slope
The purpose of room influence is to enable the controller to exactly reach and maintain
the respective setpoint.
This type of control provides PI control during the control process, the I-part ensures
that the required room temperature will be reached and maintained with no offset. .
This type of control is used primarily in plants or buildings where a room is suited as a
reference room for the room temperature.
Prerequisites for this type of control:
Outside sensor connected
Room unit connected
Room authority set in the range 0…100 %
The compensating variables used for weather-compensated control with room influence
are:
The composite outside temperature
The setpoint / actual value deviation of the room temperature
The setpoint of the flow temperature is continuously shifted in function of the composite
outside temperature (via the heating curve). Also, any room temperature deviation pro-
duces an instant parallel displacement of the heating curve. The correlation between
the extent of the temperature deviation and the degree of displacement is defined by
the room authority, which is dependent on
the selected authority
the setpoint / actual value deviation of the room temperature
the selected heating curve slope
Weather-compensated
control
Room temperature-
compensated control
Weather-compensated
control with room
influence
19

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens RVP201 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Siemens RVP201

Siemens RVP201 Installationsanweisung - Deutsch, Englisch, Holländisch, Dänisch, Französisch, Italienisch, Spanisch, Schwedisch, Finnisch - 26 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info