555849
6
Zoom out
Zoom in
Vorherige Seite
1/8
Nächste Seite
CE2N2462E / 09.12.1998 Siemens Building Technologies
6/8 Landis & Staefa Division
When connecting an external switching contact to the controller's terminals A6-MD, the
operating mode can be selected from a remote location:
Contact closed: controller is in standby mode
Contact open: controller uses the operating mode selected with the slider
The wires of the measuring circuits carry extra low voltage
The wires to the actuator and the pump carry AC 24...230 V
The local electrical regulations must be complied with
Detector cables must not be run parallel to mains carrying cable for loads such as
actuator, pump, burner, etc. (safety class II to EN 60730)
The maximum limitation of the boiler temperature may not be used as a safety function.
For that purpose a thermostat or safety limiter must be connected at terminals L-F1/F4
Setpoint adjustments:
Normal temperature (in °C room temperature)
Setback (in °C room temperature)
D.h.w. (only with the RVP210)
Settings to be made by the heating engineer:
Slope of heating curve
Authority of room temperature
ECO heating limit
Maximum limitation of the flow or boiler temperature
Type of regulating unit (mixing valve or burner)
Type of control (three- or two-position)
Frost protection activated or deactivated
Priority of d.h.w. heating (only with the RVP210)
The controller is supplied complete with installation instructions and operating instruc-
tions.
- conformance to
EMC directive 89/336/ EEC
Immunity EN 50082-2
Emissions EN 50081-1
Low voltage directive 73/23/ EEC
Safety EN 60730-1
Rated operating voltage AC 230 V ±10 %
Frequency 50 Hz
Power consumption 7 VA
Degree of protection (cover closed) IP40 D EN 60529
Safety class II EN 60730
Permissible ambient temperatures
Transport 25...+70 °C
Storage 5...+55 °C
Operation 0...50 °C
Weight (net) 0.72 kg
Test class II
Rated voltage AC 230 V
Rated current 2 (2) A
Contact current at AC 24...90 V 0.1...2 A, cos ϕ >0.5
Contact current at AC 90...250 V 0.02...2 A, cos ϕ >0.5
Rated current of ignition transformer 1 A max.(30 s max.)
Switch-on current of ignition transformer 10 A max.(10 ms max.)
Setpoint of normal room temperature 20 ±0...8 °C
Setback for reduced room temperature 12...0 K
Setpoint of d.h.w. temperature (only with the RVP210) 10...60 °C
Slope of heating curve 0.25...4
Max. limit of flow or boiler temperature 8...100 °C
ECO heating limit 10...+8 °C (referred to normal setpoint)
Authority of room temperature 0...100 %
Switching differential with two-position control 1...20 K
Analog time switches 12 hours
Digital weekly time switch with backup battery
Switching contact
Notes
Engineering
Commissioning
Technical data
General data
Output relays
Setting ranges
Backup of time switches
6

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens RVP210 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info