Siemens Basic Documentation RVP340, RVP350, RVP351 CE1P2545en
Building Technologies 4 Acquisition of measured values 15.03.2011
In the event of a short-circuit or an interruption of one of the 2 measuring circuits,
the controller continues to operate with the other measuring circuit. An error mes-
sage is delivered.
If both measuring circuits do not produce a valid measured value, 2 error mes-
sages are delivered. D.h.w. is no longer heated; the charging pump will be deacti-
vated.
If there is neither an interruption (thermostat open) nor a short-circuit (thermostat
closed) in measuring circuit B31, an error message is delivered. D.h.w. is no longer
heated; the charging pump will be deactivated.
If there is neither an interruption (thermostat open) nor a short-circuit (thermostat
closed) in one of the measuring circuits, an error message is delivered. The con-
troller continues to operate with the correctly working measuring circuit.
If there is neither an interruption (thermostat open) nor a short-circuit (thermostat
closed) in both measuring circuits, 2 error messages are delivered. D.h.w. is no
longer heated; the charging pump will be deactivated.
In the event of a short-circuit or an interruption of one of the 2 measuring circuits,
the controller continues to operate with the other measuring circuit, if possible. An
error message is not delivered.
If both measuring circuits do not produce a valid measured value, an error mes-
sage is delivered. D.h.w. is no longer heated; the charging pump and the collector
pump will be deactivated.
In the event of a short-circuit or an interruption of one of the 2 measuring circuits,
the controller continues to operate with the other measuring circuit. An error mes-
sage is delivered.
If both measuring circuits do not produce a valid measured value, 2 error mes-
sages are delivered. D.h.w. is no longer heated; the charging pump and the collec-
tor pump will be deactivated.
If a measured value of the d.h.w. temperature is not available and the temperature
is queried, the QAW70 room unit displays ---.
4.7 Collector temperature (B6)
4.7.1 Type of sensor
The collector temperature is acquired by a Siemens sensor operating with a sens-
ing element LG-Ni1000 and an extended measuring range.
4.7.2 Error handling
In the event of an interruption of the measuring circuit, an error message is deliv-
ered with a delay of 12 hours and the collector pump is deactivated. This means
that solar d.h.w. heating is no longer provided.
2 storage tank sensors
(operating line 126 = 1)
1 storage tank thermostat
(operating line 126 = 2)
2 storage tank thermo-
stats (operating line
126 = 3)
1 storage tank sensor for
solar d.h.w. heating
(operating line 126 = 4)
2 storage tank sensors
for solar d.h.w. heating
(operating line 126 = 5)
22

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens RVP340 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Siemens RVP340

Siemens RVP340 Bedienungsanleitung - Deutsch - 108 seiten

Siemens RVP340 Bedienungsanleitung - Französisch - 112 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info