Siemens Basic Documentation RVP340, RVP350, RVP351 CE1P2545en
Building Technologies 9 Function block: Space heating 15.03.2011
9 Function block: Space heating
This function block performs the automatic ECO function, the optimization
functions with boost heating and quick setback, plus room influence.
9.1 Operating lines
Line Function, parameter Factory setting (range) Unit
61 NORMAL heating limit (ECO day) 17.0 (--.- / 5...25) °C
62 REDUCED heating limit (ECO night) 5.0 (--.- / –5...25) °C
63 Building time constant 20 (0...50) h
64 Quick setback 1 (0 / 1)
65 Room temperature source A (0…3 / A)
66 Type of optimization 0 (0 / 1)
67 Maximum heating up period 00:00 (00:00...42:00) h
68 Maximum early shutdown 0:00 (0:00...6:00) h
69 Maximum limitation room temperature --.-- (--.- / 0...35) °C
70 Influence of room temperature (gain factor) 4 (0...20)
71 Boost of room temperature setpoint on boost heating 5 (0...20) °C
9.2 Automatic ECO function
The automatic ECO function controls space heating depending on demand. It gives
consideration to the progression of the room temperature depending on the type of
building structure as the outside temperature varies. If the amount of heat stored in
the house or building is sufficient to maintain the room temperature setpoint cur-
rently required, the heating is switched off.
The automatic ECO function ensures that the heating system operates only, or
uses energy only, when indeed required.
9.2.1 Compensating and auxiliary variables
The compensating and auxiliary variables considered by the automatic ECO func-
tion are the progression of the outside temperature and the heat storage capacity
of the building.
The following variables are taken into account:
The building time constant: This is a measure of the type of building structure
and indicates how quickly the room temperature would vary if the outside tem-
perature suddenly changed. The following guide values can be used for setting
the building time constant: 10 hours for light, 25 hours for medium, and 50 hours
for heavy building structures
The current outside temperature (T
A
)
The composite outside temperature (T
AM
). It is the mean value of …
the current outside temperature,
the outside temperature filtered by the building time constant
Compared with the current outside temperature, the composite outside tempera-
ture is attenuated. Hence, it represents the impact of short-time outside tempera-
ture variations on the room temperature as they often occur during intermediate
seasons (spring and autumn).
The attenuated outside temperature (T
AD
): It is generated by double-filtering the
current outside temperature by the building time constant. This means that – in
comparison with the current outside temperature – the attenuated outside tem-
perature is considerably dampened. This ensures that no heating is provided in
30

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens RVP351 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Siemens RVP351

Siemens RVP351 Bedienungsanleitung - Deutsch - 108 seiten

Siemens RVP351 Bedienungsanleitung - Französisch - 112 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info