Siemens Basic Documentation RVP340, RVP350, RVP351 CE1P2545en
Building Technologies 11 Function block: Boiler 15.03.2011
If there is no more deviation before the minimum burner running time has elapsed,
the burner will nevertheless continue to operate until that time has elapsed (burner
cycling protection). This means that the minimum burner running time has priority.
Maximum limitation of the boiler temperature is maintained, however, which always
leads to burner shutdown.
T
Kw
+ 0,5
*
SD
0
1
2522D14
T
K
T
Kw
T
Kw
- 0,5
*
SD
T
Kx
t
Y
B
SD Switching differential T
Kw
Boiler temperature setpoint
t Time T
Kx
Actual value of boiler temperature
T
Kx
Boiler temperature Y
B
Burner control signal
Note on setting: When controlling a 1-stage burner, the reset integral of the second
stage should be set to zero.
11.4.2 Control with 2-stage burner
For 2-position control with a 2-stage burner, the variables that can be set are the
switching differential and the minimum burner running time – the latter now apply-
ing to both stages – plus the following variables:
The release integral (FGI) for the second stage. This is the variable generated
from the progression of temperature (T) and time (t). If the maximum limit is ex-
ceeded, the second burner stage is released and can be switched on. Prerequi-
site is that the minimum locking time for the second stage has elapsed.
FGI =
t
dtT
0
where: T = ( w 0.5
*
SD x ) > 0
The reset integral (RSI). This is a variable generated from the progression of
temperature and time. If the maximum limit is exceeded, the burner is locked
and shuts down.
RSI =
t
dtT
0
where: T = ( x w + 0.5
*
SD ) > 0
The minimum locking time for the second stage, which is the period of time on
completion of which the second stage can switch on at the earliest
The controller compares the actual value of the flow temperature with the setpoint.
If it falls by half the switching differential (x < w 0.5
*
SD) below the setpoint, the
first burner stage is switched on. At the same time, the minimum waiting time for
the second burner stage commences and the release integral is being generated.
The controller ascertains for how long and by how much the flow temperature re-
mains below w 0.5
*
SD. It continuously generates the integral based on the pro-
gression of temperature and time.
If, on completion of the minimum locking time, the flow temperature lies below
w 0.5
*
SD, and the release integral reaches the set maximum limit, the second
burner stage is released and switched on. The flow temperature rises.
If the flow temperature exceeds the setpoint by half the switching differential
(x = w + 0.5
*
SD), the second burner stage is switched off again, but remains
Setting parameters
Control process
47

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Siemens RVP351 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Siemens RVP351

Siemens RVP351 Bedienungsanleitung - Deutsch - 108 seiten

Siemens RVP351 Bedienungsanleitung - Französisch - 112 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info