INFORMATION ON SERVICING
1) Checks to the area
Prior to beginning work on systems containing
flammable refrigerants, safety checks ar
necessary to ensure that the risk of ignition is
minimised. For repair to the refrigerating
system, the following precautions shall be
complied with prior to conducting work on the
system.
2) Work procedure
Work shall be undertaken under a controlled
procedure so as to minimise the risk of a
flammable gas or vapour being present while the
work is being performed.
3) General work area
All maintenance staff and others working in the
local area shall be instructed on the
nature of work being carried out. Work in confine
spaces shall be avoided. The area
around the workspace shall be sectioned off
Ensure that the conditions within the area
have been made safe by control of flammabl
material.
4) Checking for presence of refrigerant
The area shall be checked with an appropriate
refrigerant detector prior to and during
work, to ensure the technician is aware of
potentially flammable atmospheres. Ensur
that the leak detection equipment being used is
suitable for use with flammabl
refrigerants, i.e. non-sparking, adequately sealed
or intrinsically safe.
5) Presence of re extinguisher
If any hot work is to be conducted on the
refrigeration equipment or any associated parts,
appropriate fire extinguishing equipment shall be
available to hand. Have a dry powder or
CO2 fire extinguisher adjacent to the charging
area.
6) No ignition sources
No person carrying out work in relation to a
refrigeration system which involves exposing
any pipe work that contains or has contained
flammable refrigerant shall use any source
of ignition in such a manner that it may lead to the
risk of fire or explosion. All possible
ignition sources, including cigarette smoking,
should be kept sufficiently far away from t
site of installation, repairing, removing and
disposal, during which flammable refrigeran
can possibly be released to the surrounding
space. Prior to work taking place, the area
around the equipment is to be surveyed to make
sure that there are no flammabl
hazards or ignition risks. “No Smoking” signs shall
be displayed.
7) Ventilated area
Ensure that the area is in the open or that it is
adequately ventilated before breaking into
the system or conducting any hot work. A degree
of ventilation shall continue during the
period that the work is carried out. The ventilation
should safely disperse any released
refrigerant and preferably expel it externally into
the atmosphere.
8) Checks to the refrigeration equipment
Where electrical components are being changed,
they shall be fit for the purpose and t
the correct specification. At all times the
manufacturers maintenance and service
guidelines shall be followed. If in doubt consult the
manufacturers technical department
for assistance.
The following checks shall be applied to
installations using flammable refrigerants
– The charge size is in accordance with the room
size within which the refrigerant
containing parts are installed;
The ventilation machinery and outlets are
operating adequately and are not obstructed;
If an indirect refrigerating circuit is being used,
the secondary circuit shall be checked
for the presence of refrigerant;
Marking to the equipment continues to be visible
and legible. Markings and signs that
are illegible shall be corrected;
Refrigeration pipe or components are installed in
a position where they are unlikely to
be exposed to any substance which may corrode
refrigerant containing components,
unless the components are constructed of
materials which are inherently resistant to
being corroded or are suitably protected against
being so corroded.
9) Checks to electrical devices
Repair and maintenance to electrical components
shall include initial safety checks and
component inspection procedures. If a fault exists
that could compromise safety, then no
electrical supply shall be connected to the circuit
until it is satisfactorily dealt with. If the
fault cannot be corrected immediately but it is
necessary to continue operation, an
adequate temporary solution shall be used. This
shall be reported to the owner of the
equipment so all parties are advised.
Initial safety checks shall include:
That capacitors are discharged: this shall be
done in a safe manner to avoid possibility
of sparking;
That there no live electrical components and
wiring are exposed while charging,
recovering or purging the system;
That there is continuity of earth bonding.
26
26

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Sogo SS-1287 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info