Special functions
7.2.1.1. - Speed when „On“
This menu determines the calculated and displayed speed of the pump. If e.g. 30% is
set here and the signal set in „PWM on/0-10V on“ is put out, 30% speed is displayed.
When the signal set in „PWM max/0-10V max“ is put out, 100% speed is displayed.
Everything in between is calculated accordingly.
7.3. - Speed control
7.3.1. - Speed control Modes
The following speed variants are available here:
Off: There is no speed control. The connected ventilator is only switched on or off with
full speed.
ModeV1: After the purging time the controller switches to the set max. speed. If the
temperature difference ∆T between the reference sensors (collector and sensor) is less
than the set value, then the speed is decreased by one stage after the control time
elapses. If the temperature difference between the reference sensors is greater than
the set value, then the speed is increased by one stage after the control time elapses.
If the controller has adjusted the speed of the ventilator down to the smallest stage and
the ∆T between the reference sensors is ∆T off, the ventilator is switched off.
ModeV2: After the purging time the controller switches to the set min. speed. If the
temperature difference ∆T between the reference sensors (collector and sensor) is
greater than the set value, then the speed is increased by one stage after the control
time elapses. If the temperature difference ∆T between the reference sensors is below
the set value, then the speed is decreased by one stage after the control time elapses.
If the controller has adjusted the speed of the ventilator down to the smallest stage and
the ∆T between the reference sensors is T∆off, the ventilator is switched off.
ModeV3: After the purging time the controller switches to the set min. speed. If the
temperature at the reference sensor (collector) is greater than the setpoint to be set
subsequently, then the speed is increased by one stage after the control time expires.
If the temperature at the reference sensor (collector) is less than the setpoint to be set
subsequently, then the speed is decreased by one stage after the control time expires.
During this time period, the ventilator is running with full speed (100 %) to ensure
trouble-free startup. After this time has passed, the ventilator is set to speed control
and is set to max. speed or min speed, depending on the speed control variant „7.2.1.
- Modes“ auf Seite 23 chosen. Purging time can not be applied with PWM or 0-10V
output.
7.3.2. - Purging time
Sweep time determines the inertia of the speed control to prevent strong uctuations
in temperature. Sweep time is the timespan for a complete change from minimum to
maximum ventilator speed.
7.3.3. - Sweep time
23

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Sorel AIR TDC wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Sorel AIR TDC

Sorel AIR TDC Bedienungsanleitung - Deutsch - 32 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info