8.10 Menu „02 Settings“ for
Programme 10
At first, the same settings as in programme 1 must be done and
afterwards, the parameters for the charge of the second storage
tank must be set. Generally, there is no parallel operation of pump
R1 and pump R2.
Further adjustments for the priority settings must be done under
the item 10.2.
Tmax S3
Desired maximum solar temperature of storage tank 2 at sensor
S3. If the set temperature is exceeded at S3, the pump at R2
switches off and the storage tank is not charged any longer at
what the shift hysterese amounts 2°C.
Setting range:0...120°C Default value: 60°C
T R2
Here the temperature difference must be set which must be
exceeded between the collector sensor and the sensor S3 of
the second storage tank for the solar heat charge///transfer into
the second storage tank via the pump R2 to begin.
The heat is charged///transferred into this storage tank until the
temperature difference has fallen to 1/3 of the set value.
Setting range:6...18K Default value: 10K
Priority
It must be set which storage tank (storage sensor) shall be
charged with priority. The charge of the lower-level storage tank
is interrupted in regular intervals to prove that the temperature
rise at the collector submits a charge of the prior storage tank.
Setting range:S2 / S3 Default value: S2
Tnom
The lower-level storage tank is not charged until the set Tnom
value is exceeded at the storage sensor of the prior storage tank.
Setting range:0...90°C Default value: 30°C
8.11 Menu „02 Settings“ for
Programme 11
At first, the same settings as in programme 1 must be done and
afterwards, the additional difference for the charge into the
sequence storage tank must be set.
Tmin S2
The set minimum storage temperature must be exceeded in the
solar storage tank at S2 for a heat discharge into the sequence
storage tank to be released.
Setting range:0...90°C Default value: 50°C
Tmax S3
Desired maximum storage temperature at sensor S3 in the
sequence storage tank. If the set temperature is exceeded at
S3, the pump at R2 switches off at what the shift hysterese
amounts 2°C.
Setting range:0...120°C Default value: 60°C
T R2
Here the temperature difference must be set which must be
exceeded between the solar storage sensor S2 and the sequence
storage sensor S3 for a heat discharge into the sequence storage
tank to begin.
The heat is recharged until the temperature difference has fallen
to 1/3 of the set value.
Setting range:6...18K Default value: 10K
8.6 Menu „02 Settings“ for
Programme 6
At first, the same settings as in programme 1 must be done and
afterwards, the parameters for the second storage zone of the
storage tank must be set. Further adjustments for the priority
settings must be done under the item 10.2.
Tmax S3
Desired maximum solar storage tank temperature at the upper
storage sensor S3. If the set temperature is exceeded at sensor
S3, the valve at R2 switches off at what the shift hysterese
amounts 2°C.
Setting range:0...120°C Default value: 60°C
Priority
It must be set which storage tank area (storage sensor) shall be
charged with priority. The charge of the lower-level storage part
is interrupted in regular intervals to prove that the temperature
rise at the collector submits a charge of the prior storage area.
Setting range:S2 / S3 Default value: S2
8.7 Menu „02 Settings“ for
Programme 7
The same settings as in programme 1 must be done. After
exceeding of the difference „T R1“, the primary pump R2
switches on, though.
The secondary pump R1 does not switch on before the
temperature at the forerun sensor S3 is higher than at the storage
sensor S2. Pumps R1 and R2 switch off via sensors S1 and S2.
The rotational speed of the secondary pump R1 is controlled via
the forerun sensor S3 and the storage sensor S2.
8.8 Menu „02 Settings“ for
Programme 8
The same settings as in programme 1 must be done. The set
value of the minimum collector temperature „Tmin S1“ is for both
collector areas. The warmer collector is always perfused via the
change-over valve R2 when the solar pump R1 is active. The
change-over hysterese amounts 8°C.
The reference sensor to control the rotational speed and to switch
off the solar pump R1 is always the sensor of the collector area
which is being perfused.
8.9 Menu „02 Settings“ for
Programme 9
At first, the same settings as in programme 1 must be done and
afterwards, parameters for the charge of the second storage tank
must be set. Further adjustments for the priority settings must
be done under the item 10.2.
Tmax S3
Desried maximum solar temperature of storage tank 2 at sensor
S3. If the set temperature is exceeded at S3, the valve at R2
switches off and the storage tank is not charged any longer at
what the shift hysterese amounts 2°C.
Setting range:0...120°C Default value: 60°C
Priority
It must be set which storage tank (storage sensor) shall be
charged with priority. The charge of the lower-level storage tank
is interrupted in regular intervals to prove that the temperature
rise at the collector submits a charge of the prior storage tank.
Setting range:S2 / S3 Default value: S2
Tnom
The lower-level storage tank is not charged until the set Tnom
value is exceeded at the storage sensor of the prior storage tank.
Setting range:0...90°C Default value: 30°C
5

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Sorel DR3 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Sorel DR3

Sorel DR3 Bedienungsanleitung - Deutsch - 8 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info