Mode M2: The controller changes to the set min. speed after the Speed. If the temperature difference T between the reference
sensors is above the set switch on temperature difference ∆T R1, the speed will be increased. If the temperature difference ∆T
between the reference sensors is below the set switch on temperature difference ∆T R1, the speed will be reduced. If the con-
troller has decreased the speed of the pump to the smallest level and the ∆T between the reference sensors is still only Toff, the
pump will be turned off.
Mode M3: The controller changes to the set min. speed after the Speed. If the temperature on the reference sensors is above the
set value to be set in the following, the speed will be increased. If the temperature on the reference sensors is below the set value
to be set in the following, the speed will be reduced.
Purging time
For this time, the pump runs with its full speed (100%) in order to guarantee a secure start-up. Only after expiration of this purging
time will the pump have a controlled speed and will switch, depending on the set variant, to the max. or min. speed. Speed.
Sweep time
With the control time, the inertia of the speed control is determined in order to prevent strong temperature deviations as much as
possible. The timespan is entered here, which is needed for a complete cycle from minimum speed to maximum speed.
Max. Speed
The maximum speed of the pump is determined here. During the setting, the pump runs in the respective speed and the flow can
be determined.
The specified percentages are variables, which may deviate more or less strongly depending on the system, pump
and pump level. 100% is the maximum possible power of the controller.
Min. Speed
The minimum speed of the pump is determined here. During the setting, the pump runs in the respective speed and the flow can
be determined.
The specified percentages are variables, which may deviate more or less strongly depending on the system, pump
and pump level. 100% is the maximum possible power of the controller.
Setpoint
This value is the control setpoint for mode 3 see " Variant " on page 24, only version 2.3, and 4. If this value is below at the
sensor, the speed is reduced. When it is exceeded, the speed is increased.
Sensor Calibration
Deviations in the temperature values displayed, for example. due to cables which are too long or sensors which are not posi-
tioned optimally can be compensated for manually here. The settings can be made for each individual sensor in steps of 0.5 °C.
Settings are only necessary in special cases at the time of initial commissioning by the specialist. Incorrect meas-
urement values can lead to unpredictable errors.
Relay functions
Free relays, i.e., relays not used in a basic scheme, can be assigned to various additional functions. Every additional function can
only be assigned once. See all additional functionssee " Function overview " on page 28.
R1 to R4: mechanical relay 230V
V1 and V2: PWM and 0-10 V output
Please pay special attention to the relay’s technical information (see "Specifications“).
The symbols shown here are displayed on the main overview screen when the special function is activated.
Heat quantity
Constant flow
If “Constant flow” is activated as the type of heat quantity metering, the approximate heat from the manually entered values for
antifreeze, its concentration and the flow from the system and the measured sensor values from the collector and storage are cal-
culated. Additional information about antifreeze, its concentration and the flow of the system is required. Additionally through the
setting offset ∆T, a correction factor can be set for the heat quantity collection. Since the collector temperature and the storage tem-
perature can be used for the heat quantity metering, depending on the system, there may be deviations from the displayed col-
lected temperature to the actual previous temperature or the displayed storage temperature to the actual return temperature.
Through the setting Offset ∆T, this deviation can be corrected.
25
25

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Sorel LHCC wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Sorel LHCC

Sorel LHCC Bedienungsanleitung - Deutsch - 46 seiten

Sorel LHCC Bedienungsanleitung - Französisch - 45 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info