2.6 SAFETY VALVE
In the direct vicinity of the H2O fireplace insert, a type-tested safety valve
(e.g. make Syr, type 1915) with an activation overpressure of max. 3.0 bar
must be mounted in the flow line. When installing, the manufacturer's
specifications (e.g. ambient temperature) of the safety valve must be taken
into account. A shut-off possibility must not be integrated in the system
between the safety valve and the H2O fireplace insert This could render
the safety device inoperable. Moreover, all necessary safety devices must
be integrated in the entire system in such a manner that safe operation is
ensured. A separate safety valve must also be installed, if such a safety
valve is installed at a different point in the entire system (comply with TRD
721!).
2.7 RETURN FLOW TEMPERATURE BOOST
The H2O fireplace insert must only be operated with a suitable return flow
boost. In operation the return flow temperature must be at least 55°C/60°C
(see „1.3 Technical data“). So that this temperature is ensured, a circulation
pump must be installed in such a manner that it only starts up if a water
temperature of 60-65°C has been reached in the heat exchanger. This must
be executed with the pump thermostat (included in the scope of delivery,
e.g. JUMO, heatTHERM, Afriso) (see „2.9 Thermal pump controller“). To
avoid temperatures below the local dewpoint and thus deposits on the water
heat exchanger, a regulated return flow temperature boost must always
be installed. The longer the pipelines between the return flow temperature
boost and the fireplace insert, the longer the time the temperature can be
below the dewpoint in the fireplace insert, because this heating water must
only be warmed at heating up. Consequently, it is recommended to install
the return flow temperature boost unit directly, however where it is easily
accessible, in the vicinity of the fireplace insert.
Please note: If there is no return flow temperature boost unit, or if the
return flow temperature boost is not functioning effectively, we can assume
2.4 MINIMUM CROSS SECTIONS - CONVECTION AIR
The minimum cross sections for convection air (supply air and recirculat-
ing air) in the cladding or in the heating chamber must be designed as
described in the technical data (chapter „1.3 Technical data“).
The Regulations of the German Tiled Stove and Air Heating Constructors
Association (TR-OL 2006) must always be taken into account.
The specification of opening sizes for convection air applies for air velocities of
0.75 m/s in fireplaces (hot-air systems or radiant heating). If a combination of
fireplace and closed system (hypocausts) is created, there are smaller openings
for supply air and circulating air, since the energy output via the heating cham-
ber surface should be considered.
2.5 VENTILATION AND DRAINING
A 1/2" draining possibility must be provided at the low point of the fireplace
insert and of the pipe system. To vent the water heat exchanger the vent
possibilities cited in Fig. 2a-2f must be available. In the direct vicinity of the
vent valve a sufficiently large opening must be provided in the lining where
the upper vent is used! On the other hand, the lower vent (in the area of the
connections on the rear) can be reached and used through the inspection
opening in the combustion chamber. After commissioning, the insert must
be vented several times because the heating water outgases due to the high
temperatures. It must be ensured at all times that the system is adequately
filled with water and vented. This must be particularly checked after longer
periods of system downtime.
The stipulations of TR-OL regarding the free cross-section of the vent open-
ings, as well as the maximum supply air temperatures of 75 °C must be
strictly complied with! Non-lockable recirculating air openings and supply
air openings are recommended to exclude the possibility of accumulated
heat within the combustion chamber!
24

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Spartherm Mini H2O wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Spartherm Mini H2O

Spartherm Mini H2O Bedienungsanleitung - Deutsch - 44 seiten

Spartherm Mini H2O Bedienungsanleitung - Holländisch - 44 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info