- 18 - - 19 -
HBS 300 Highbay / HBS 200 Highbay stay-ON time
Stay-ON time is the period of time lights remain
ON after detecting the last movement. This time
can be set from 15 sec. to 30 min. Factory set-
ting is 15 min.
Time
ON
1234
Low
High
Low
High
After setup and commissioning tests are
complete, adjust the stay-ON time and light
level settings to fit the application needs.
Time Delay DIP Switch
1
ON
ON
OFF
ON
ON
OFF
OFF
OFF
N/A
2
ON
OFF
ON
OFF
ON
ON
OFF
OFF
N/A
3
ON
OFF
ON
ON
OFF
OFF
ON
OFF
N/A
4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
Time
15 sec
1 min
5 min
10 min
15 min
20 min
25 min
30 min
override
DIP swich for setting HBS 300 Highbay / HBS 200 Highbay stay-ON time
Time
Manual
override
Setting and starting up HBS 300 Highbay / HBS 200 Highbay
Lens covers
Lens covers can be used to adjust the high bay
sensor's coverage as needed.
The plastic shrouds simply push on to the front
of the HBS 300 Highbay or HBS 200 Highbay.
LC4 shroud for reducing
HBS 300 Highbay reach
LC5 180° half-moon lens cover for
HBS 300 Highbay
LC1 aisle start cover for
HBS 200 Highbay
10
20
30
40
40 ft
13 ft
50 ft
53 ft
LC1
radial
tangential
10
20
30
40
40 ft
LC4
30 ft
22 ft 22 ft
30 ft
10
20
30
40
LC5
40 ft
35 ft
22 ft
40 50
4
Wireless interconnection by means of optional MF1 wireless module
An MF1 wireless group control module with
wireless group control capability can be added
to any HBS 300 Highbay or HBS 200 Highbay
sensor.
Stay-ON time is at least 30 sec. when using the
MF 1.
EAN MF1 .................................. 4007841736712
5
MF1 safety precautions / installation
n Please only plug the module in with the mains
power supply switched OFF. (see Fig.)
n Only use genuine replacement parts.
n The wireless module must not be plugged in
when using the Install mode.
Technology
868 MHz, bidirectional. Reach up to 100 m,
depending on the line of vision, walls, wall pro-
jections, corridor corners, wall reflections etc.
Recommendation: reliable wireless link up to
30 m is ideal.
The optional wireless receiver extends lighting
control within a group of luminaires, making it
the ideal accessory for intelligently intercon-
necting high-bay sensors.
RM 50 Highbay wireless receiver
Wireless communication
STEINEL wireless lighting controllers are
grouped together through a DIP switch address.
When a wireless presence sensor in the group
detects a movement, all devices in that group
will be switched ON. For example, when a
sensor detects the presence of a person and
switches the light ON, this switching command
will be sent to all wireless devices in this group.
All these devices then switch the light ON. Light
only switches OFF when command signals stop
being sent to the group and the last device's
stay-ON time has elapsed. The switching sig-
nals are limited by the devices' wireless reach.
Setting and starting up RM 50 Highbay (MF1)
Groups
The 5 position DIP switch on all STEINEL wire-
less devices can be used for setting 32 different
addresses or groups.
All devices in a group must have the same DIP
switch setting. The ON switching commands
only apply within a group.
12345
12345
GB
10

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Steinel MF 1 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info