4.6 Auxiliary electric cable connection
All 3 auxiliary cables to connect are equipped
with a polarized connector.
One cable is necessary for generator operation,
while the other 2 are optional cables.
Cable from the generating set to the control
panel (mandatory). It is included in the stan-
dard supply and is 5 metres long. Check that
its length is sufficient to cover the chosen rout
between the generating set and the control
panel. Optional cables in longer sizes are
also available.
After leading the cable through the cable out-
let block (Fig.11 Ref.1) connect the white
connector to the fixed connector (Fig.13 Ref.
9) provided inside the generating set, check-
ing that the plugging direction is correct.
Cable from the generating set to the auxiliary
fuel pump and fuel tank reserve (optional).
From the three-pole connector (Fig.13 Ref.8)
it is possible to take two cables to supply
electric input to an auxiliary fuel pump; also
see paragraph 4.8.
From the same connector (Fig.13 Ref.8) it is
also possible to take the signal for tank fuel
warning; also see paragraph 4.10.
Cable from the generating set to the auxiliary
battery charger (optional). From the bipolar
connector (Fig.13 Ref.6) it is possible to de-
rive supply for an RCB battery charge regula-
tor via two 4 mm
2
cables; also see para-
graph 4.11.1.
4.7 Electronic control panel connection
Choose your required position for the control
panel inside the vehicle and drill a 30 x 32 mm
rectangular hole. After letting out of the hole the
connecting cable coming from the generating set
(paragraph 4.6) connect the cable black connec-
tor on the back of the electronic control panel. Fix
the electronic control panel (Fig.14) by using 3 x
20 mm self-tapping screws, making sure that the
rear part does not interfere with other surfaces.
Apply light pressure to fix the plastic frame, until
the anchoring tabs click in.
4.8 Auxiliary (optional) fuel pump connection
If the distance that fuel must cover between the
fuel tank and the generating set is too long or the
tank is installed at a lower level than the generat-
ing set, the fuel pump installed inside the gener-
ating set may find it difficult to take fuel in from
the tank by suction. In this case, an auxiliary op-
tional fuel pump (code 00507) should be installed
as close as possible to the tank for easy priming.
12

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Telair Energy 2510b wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info