You can set values between 10 ˚C and 25 ˚C. This function can be
deactivated by setting the value 99 ˚C.
6.5.8. Optimum Start
6.5.8.1 Room Temperature Control Mode
1. Turn the rotary switch to position MENU.
2. With button ▲ go to
settings. Confirm with the OK button.
3. With button ▲ go to
optimisation. Confirm with the OK button.
4. Select with button ▲ minutes (min: 0, max: 60 minutes;
default value is 0, that means optimisation is switched off).
Confirm with the OK button.
If value 15 is adjusted it means 15 minutes/°C.
Example
- Actual temperature is 18 °C
- Comfort temperature is 21 °C
- Difference between Lower and Comfort temperature is 3 °C
Value for optimisation 15 minutes/°C
It is wished to have at 7:00 Comfort, the heating starts at 6:15
hours. It starts 3 °C x 15 minutes = 45 minutes earlier than 7:00
o´clock. If program switches from Comfort to Lower temperature
optimisation is not used. That means there is comfort temperature
until programmed time. Lower temperature does not start earlier.
6.5.8.2 Weather Compensation Mode
1. Turn the rotary switch to position MENU.
2. With button ▲ go to
settings. Confirm with the OK button.
3. With button ▲ go to
optimisation. Confirm with the OK button.
4. Select with button ▲ minutes (min: 0, max: 60 minutes;
default value is 0, that means optimisation is switched off).
Confirm with the OK button.
If value 15 is adjusted it means 15 minutes/°C flow temperature.
Example
- Control temperature is according to calculated curve: at 10 °C
- Outside temperature 45 °C flow temperature
- Lower temperature is flow temperature –30 °C
Value for optimisation 15 minutes/°C
It is wished to have at 7:00 Comfort, the heating starts at 6:15
hours. It starts 3 °C x 15 minutes = 45 minutes earlier than 7:00
o´clock.
If program switches from Comfort to Lower temperature optimisa-
tion is not used. That means there is Comfort temperature until
programmed time. Lower temperature does not start earlier.
Switch from weather compensation control to room
temperature control and versus
If customer press for more than 5 seconds OK button it changes
from weather compensation control to room temperature control
or versus. Weather compensation can only be activated if outside
temperature sensor is connected to the boiler.
We show weather compensation mode with a small symbol in the
display ##.