11. PLACING THE UNIT (first read “General instructions”)
Please note: Before placing the unit, we recommend you first read Chapter 7
“Concentric flue system” on page 11.
11.1 Connection to the gas pipes
You can determine where the gas pipes will be placed, dependent on the layout. Ensure control equipment is not
twisted during installation and there is no excessive tension. Accessibility of various connection points in relation
to components need to be maintained. After installation, check the connections for tightness in relation to gas.
Use a 1/2“ gas tap with connection. Ensure the gas pipes are dirt-free and sand-free, and gas and
combustion products from various parts and functioning is correct. The gas connection should only be
undertaken when the electricity supply is disconnected. This prevents any damage occurring to the gas control
equipment.
11.2 Preparation and installation of the unit (see also pages 37 and 38)
Remove the packaging and check the unit for possible damage.
Take the 2 lifting frames (A) out of the packaging and use them to place the unit at its intended location
Please note: place the unit on a stable surface.
Do not place the unit on its back or on its side!
The front window should now be removed in order to take the additional parts out of the unit. The side
window (s) can remain in place.
Remove the lower cover profile from the unit, see fig. B.
Loosen the screws of the lower and upper quadrants, see fig. C and D.
Next, take the packaged components out of the unit and check to make sure they are not damaged or
broken.
Situate the unit (see page 33 as an example of an installation location) in your chosen installation location
using the lifting frame (A). At the rear and the sides, the unit must have at least 25 mm clearance from
fireproof built-in materials. Install the convection set and position the supplied convection grilles at least 50
cm below the ceiling (see page 33-C) on the appropriate wall. A lowered ceiling inside the whole structure
could be a possible solution in the event of a situation with a visual obstruction.
Please note: In an installation location with masonry, a mantle iron (A) will have to be installed.
See also the detail on page 33 figures 1A and 2A for the installation of the mantle iron. The standard
mantle iron can be used for both the corner and panorama situations. The mantle iron can be
mounted against the wall, taking into account the position of the recess in the ceiling, if applicable.
The legs (page 38, figure P) of the unit can be adjusted, and if necessary shortened, see also dimensional
drawings. The adjustable feet allow fine adjustments (levelling) to be made.
Gas pipe, thermocouple and ignition cables have been placed in coils under the unit (see page 38 fig O).
Cut the binders and CAREFULLY unroll the various lines and cables to the position where the gas control
cassette is to be placed.
Fixing to the wall is effected by means of adjustable wall brackets (see figure N page 38) on top of the unit.
Fastening materials are not included.
Now determine the installation and assembly of the CC ducts and accessories. Please refer to Chapter 7.
Take hold of the front window by its sides and move it CAREFULLY upwards, then CAREFULLY
and slowly pull the bottom of the window towards you. Next, lower the window and leave it in a safe
place where it cannot be broken or damaged. On corner models, first slide the window slightly towards
the open side (i.e. where the side glass is located) and then remove it.
Please note: the window is very fragile.
You should therefore be very careful when (re)installing the window!
Please note:
The distance between the gas cassette / control cabinet and the unit will be determined by the ca-
ble / thermocouple / line lengths from the control cabinet to the pilot burner and main burner.
The max. distance is approximately 1000 mm. (see also page 29-30). The pipes, cables and/or cou-
plings etc. should only be connected when the electricity supply is off.
23

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Thermocet Trimline 63 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Thermocet Trimline 63

Thermocet Trimline 63 Bedienungsanleitung und Installationsanweisung - Holländisch - 39 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info