602542
49
Zoom out
Zoom in
Vorherige Seite
1/52
Nächste Seite
Appendix
0020147164_04 aroTHERM Installation instructions 49
Code Meaning Cause
F.537 High-pressure switch open Coolant volume too high or too low
Vacuum insufficient (10 mbar)
Incondensable particle in the coolant circuit
Pressure switch or electrical connection faulty
Premature expansion in the liquid area of the coolant circuit (loss
of charge)
Flow quantity too high (see defined maximum flow rate)
Flow rate monitor faulty
Insufficient heat transfer in the heat exchanger
F.539 Coolant pressure too low Coolant quantity too low
Air flow too low
No thawing
The resistance heating in the condensate receiver is faulty.
4-way valve faulty
Electronic expansion valve motor faulty, or connection faulty
F.546 Sensor fault: High pressure Faulty cabling
F.554 Coolant pressure not in operating range Coolant volume too high or too low
Incondensable particle in the coolant circuit
Electronic expansion valve faulty
Premature expansion in the liquid area of the coolant circuit (loss
of charge)
Flow quantity too high (see defined maximum flow rate)
Insufficient heat exchange in the plate heat exchanger or the
ribbed pipe heat exchanger
4-way valve faulty
F.582 EEV fault Cable insulation faulty
Connection broken
F.585
Sensor fault: Temp. building circuit EEV
2)
Sensor is faulty or incorrectly connected to the main PCB
F.685 Communication fault: eBUS The product is not connected to the controller
Polarity inverted
F.750 Connection fault: Compressor Cable insulation faulty
Connection broken
F.751 Compressor: Overcurrent fault The product's voltage supply is too low
The ribbed pipe heat exchanger or heat exchanger is dirty
F.752 Fault: Inverter Inverter box damaged
The cooler inverter box is blocked.
Faulty voltage supply
The "Max. duration power supply cut-off" parameter has been
set poorly (see the "Heat pump setting parameters" section in
the appendix).
F.753 Connection fault: Inverter not recognised The connection between the main PCB and the inverter box is
damaged or broken.
The inverter box is not switched on.
The "Max. duration power supply cut-off" parameter has been
set incorrectly (see the "Heat pump setting parameters" section
in the appendix).
F.754 Fault: Fan unit The connection between the main PCB and the fan PCB is dam-
aged or broken.
The fan PCB is faulty
F.755 Fault: 4-way valve position incorrect Mechanical or electrical problem. Move the 4-way valve away from
the controller. When moving it, check that the coil voltage is correct.
F.774 Sensor fault: Air inlet temperature The temperature sensor is faulty or incorrectly connected to the
main PCB.
F.1288 Fault: SP1 cylinder temperature sensor Sensor is faulty or has not been correctly connected to the VWZ AI
heat pump control module.
Connection fault: Accessory modules Fault in the VWZ AI heat pump control module (the connection
between the display and the main PCB is faulty).
1) Sensor on the evaporator
2) Sensor on the condenser
49

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Vaillant aroTHERM VWL 55-2 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Vaillant aroTHERM VWL 55-2

Vaillant aroTHERM VWL 55-2 Bedienungsanleitung - Deutsch - 24 seiten

Vaillant aroTHERM VWL 55-2 Bedienungsanleitung - Holländisch - 20 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info