Installation instructions auroMATIC 620 0020094404_00 controller 142
Solar circuit protection function
If the solar heat exceeds the current heat requirement
(e.g. all cylinders fully charged), the temperature in the
collector array can rise steeply.
When the temperature at the collector sensor exceeds
the safe temperature the solar pump is switched off
before overheating to protect the solar circuit (pump,
valves, etc.). The pump is switched on again after coo-
ling.
This function is performed independently for each coll-
ector array.
When used with the VPM S and the VMS, the setting
parameter is blanked out. The solar pump units have
their own protection function which is always in opera-
tion.
Solar pump kick
Depending on the design, there is a time delay in
measuring the temperature of some collectors, which
can be shortened with the solar pump kick function.
Measured value of collector temperature with active
solar pump kick function:
The solar pump is switched on for 15s (solar pump kick)
if the temperature at the collector sensor >25 °C and
has risen by 2 K/hour. This transports the heated solar
fluid to the point of measurement more quickly.
If the temperature difference between the collector and
the cylinder exceeds the preset switch-on difference,
the solar pump runs for an appropriate length of time to
heat up the cylinder (differential control).
If two solar circuits are connected, the solar pump kick
function is activated for both solar circuits. The function
is performed separately for each collector array.
Special operating modes:
If the Auto mode has been selected for the cylinder cir-
cuit, the following special operating modes will influence
the reheating:
Override: Cylinder charging until the falling edge of the
next time window
Holiday: Cylinder charging deactivated
One-time charging: The cylinder is charged once to the
preset target temperature
Special output
This is a 230 V switching contact which can be confi-
gured either for reheating by means of an electric hea-
ter cartridge or for electric heating of the cylinder, or
else as a switching contact for anti-legionnaire’s disease
protection.
Starting output cylinder
The aim of this function is a quick preparing of the sto-
rage tank heating function. You can define the number
of boiler stages or heating appliances with which
recharging is started for this purpose. Drops in perfor-
mance of the cylinder should be observed to avoid
unnecessary cycles of the heating appliance during the
hot water supply.
Basic setting: 1 (heating appliance or first stage)
Switching hysteresis
A boiler switching hysteresis is required to switch the
heating appliances or stages of the boiler on or off if
heating appliances are cascaded or two-stage boilers
are used. The controller enables an individual setting of
the required switching hysteresis. The following defini-
tions have been made for their activation and deactiva-
tion:
- Activation temperature 1/3 of hysteresis below set
appliance value;
Shutdown temperature 2/3 of hysteresis above target
system value.
The
switching hysteresis is asymmetrical, so that the heater
can also switch on (especially with flat heating curves)
at higher outside temperatures (= lower target FT).
Switching hysteresis parameter: 1 - 20 K; basic value 8 K
Switch-on delay (only for cascades)
This is the time interval which should be waited out
between the activation of the previous cascade/boiler
stage and the activation of the next stage. It is used to
avoid unnecessarily switching stages on and off when
the system is close to the desired target level. The next
stage is only switched on if the current target system
value has not yet been attained or exceeded at the end
of this time.
Switch-on difference
If the difference between the collector temperature and
the lower cylinder temperature falls below the switch-on
difference, then the solar pump switches off.
Caution: The switch-on difference must be at least 1 K
smaller than the set activation difference! Therefore the
value for the setting difference is automatically adjus-
ted when 1 K is exceeded.
Note: Does not apply in combination with a VPM S or
VMS solar pump unit.
Glossary
200

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln
1

Forum

vaillant-auromatic-620

Suche zurücksetzen

  • Der Wasserspeicher wird aufgeladen aber die Heizung funktioniert nicht Eingereicht am 30-9-2017 11:10

    Antworten Frage melden
  • Hallo! bei mir kommt bei der Fehlermeldung die Fehlernummer 1 und Fehlercode 4; also der Vorlauffühler VF1 ist defekt. Wie kann man den nun aufheben? Vielen lieben Dank im voraus für eine Antwort. Eingereicht am 29-6-2014 14:06

    Antworten Frage melden

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Vaillant Auromatic 620 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Vaillant Auromatic 620

Vaillant Auromatic 620 Bedienungsanleitung - Deutsch - 52 seiten

Vaillant Auromatic 620 Bedienungsanleitung - Holländisch - 204 seiten

Vaillant Auromatic 620 Bedienungsanleitung - Französisch - 204 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info