139Installation instructions auroMATIC 620 0020094404_00 controller
Fast temperature increase
This function is used for mixer heating circuits
a) to allow the mixer to reach its target value at target
boiler temperature shortly before the boiler is swit-
ched on again despite being fully open,
b) to allow, in the event of mixing circuits with a fixed
admixture, the target mixer value (also at target hea-
ter temperature) to be reached during the morning
heating-up operation even though the fixed admix-
ture reduces the mixing circuit temperature too far,
c) in order to facilitate an optimum control range for
the operation of the mixer. (Reliable operation is only
possible if the mixer only rarely needs to move to the
"open" stop, thus ensuring a better quality of cont-
rol).
For this reason you can set a common boiler tempera-
ture excess for all mixing circuits. This will increase the
current heating circuit target value by the value set.
Fixed value circuit/Fixed value control
This function is required for special applications such as
vent curtains, fans etc. This type of control is performed
at a fixed inlet temperature regardless of the required
room temperature and outside temperature.
All operating modes can be set for this type of control.
Demand-dependent switching off of heating works in
the same way.
Floor drying
The floor-drying function is used to “heat dry” a freshly-
laid heating layer according to instructions. All opera-
ting modes, including those selected by telephone, are
interrupted if this function is activated. The flow tempe-
rature of the controlled heating circuit is controlled
according to a pre-set program regardless of the out-
side temperature.
Starting temperature: 25°C
The operating mode is displayed together with the cur-
rent day and the target inlet temperature. The current
day can be set manually.
When the function is started, the current time of the
start is saved. The change of day takes place in each
case
exactly at this time.
After a mains off/on, the floor-drying begins with
the last active day.
Frost protection delay/ Heating frost protection
The heating frost protection function ensures protec-
tion from frost in the Off and Eco modes (outside the
time windows) in the heating installationand applies to
all connected heating circuits. To prevent the system
from freezing, the required room temperature is set to
the set set-back value and the heating circuit pump is
switched on if the outside temperature falls below 3 °C.
The frost protection function can be suppressed for a
certain period of time by setting a delay time (setting
range of 0 - 23 h).
Furthermore frost protection is activated regardless of
the measured outside temperature if it is established
that the measured room temperature is lower than the
set night set back temperature with a connected remote
control device.
Heating curve
The flow temperature in heating installations, calculated
as a function of the outside temperature, is known as
the heating curve. The flow temperature in the heating
circuit gets warmer the lower the outside temperature
becomes.
Hot water priority
The hot water priority switch is only active if the DHW
cylinder in hydraulic plans 5-8 is connected directly to
the priority switching valve or the charging pump for
the boiler. Cylinder sensor TD2 remains connected to
the VRS 620. With this hydraulic connection the boiler
can charge either the buffer cylinder or the DHW cylin-
der.
Hot water reheating for drinking water cylinder
Reheating of the drinking water cylinder (SP1 with
hydraulic plan 1–4 or SP4 with hydraulic plan 5–8)
always occurs if:
the cylinder circuit is within the programmed time
window,
the cylinder temperature is 5K below the preset tar-
get value.
The activated recharging delay prevents charging of the
cylinder for the preset length of time if there is a solar
gain present. In hydraulic plan 9, the reheating is initia-
ted by the VPM W fresh water unit. See the VPM W
manual.
Legionella
Legionella are water-borne bacteria which can quickly
propagate and cause serious lung diseases. They occur
wherever heated water provides the optimum condi-
tions for multiplication. Temporarily heating the water
to above 65 °C kills off the legionella.
Glossary
197

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln
1

Forum

vaillant-vrs-620-3

Suche zurücksetzen

  • Dies ist nicht die Bedienungsanleitung der VRS 620/3, sondern die der VRS 620/2 oder /1 von 2007. Das Dokument ist identisch mit dem unter "Vaillant Auromatic 620". Bitte aktualisieren oder aus der Liste löschen, da es sonst zu Irritationen kommt. Danke. Eingereicht am 3-3-2021 08:31

    Antworten Frage melden

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Vaillant VRS 620-3 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Vaillant VRS 620-3

Vaillant VRS 620-3 Bedienungsanleitung - Deutsch - 52 seiten

Vaillant VRS 620-3 Bedienungsanleitung - Holländisch - 204 seiten

Vaillant VRS 620-3 Bedienungsanleitung - Französisch - 204 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info