Victron Energy bv / De Paal 35 / 1351 JG ALMERE / The Netherlands
Phone: (+31) (0)36 535 97 00 / www.victronenergy.com / e-mail: sales@victronenergy.com
BMS12/200
ENGLISH
1. Mount the BMS preferably on a vertical surface, for optimal
cooling.
2. Determine the rating of fuse AB (see figure and table 1).
The fuse on input AB doubles as a shunt. The BMS will limit the
input current according to the rating of this fuse. For fuse ratings
and corresponding current limit please see table 1.
Choosing the right fuse will prevent overheating of the alternator
and/or DC cabling.
3. Determine the rating of fuse LB (see figure).
This fuse should be rated in accordance with the expected load
current and the cross section of the cabling to the load.
4. Disconnect the cabling from the plus pole of the starter battery.
5. Pull off the REMOTE on/off connector to prevent unwanted
switching of the BMS.
6. Install and connect all electrical cabling and fuses AB, LB, but
leave the plus poles of the Li-ion batteries and starter battery
disconnected.
7. Daisy-chain the battery control cables between the Li-ion batteries
and connect to the BMS.
8. Connect the plus cabling to the Li-ion batteries and the starter
battery.
9. Reinsert the REMOTE on/off connector on the BMS.
The BMS is now ready for use.
Notes:
a) A battery charger can be connected to input AB instead of the
alternator.
b) The Li-ion batteries can be charged as well as discharged through
input/output LB.
c) When a load with a large electrolytic capacitor bank (such as an
inverter or inverter/charger rated at 1200VA or more) is connected
to LB, the BMS will limit its average output current during start-up
to approximately 80A. Therefore the capacity to simultaneously
start-up other DC loads is limited to 80A. Once the capacitor bank
is fully charged, the current limit increases to 400A.
BMS 12/200 specification
Maximum number of 12,8V batteries
10
Maximum charge current, Power Port AB
80A @ 40°C
Maximum charge current, Power Port LB
200A @ 40°C
Maximum continuous discharge current, LB
200A @ 40°C
Peak discharge current, LB (short circuit proof)
400A
Approximate cut-off voltage
11V
GENERAL
No load current when operating
10mA
Current consumption when switched off
5mA
Current consumption after battery discharge
cut-off due to low cell voltage
3mA
Operating temperature range
-40 to +60°C
Humidity, maximum
100%
Humidity, average
95%
Protection, electronics
IP65
DC connection AB, LB and battery minus
M8
DC connection battery plus
Faston female
6.3 mm
LED’s
Battery being charged through Power Port AB
green
Battery being charged through Power Port LB
green
Power port LB active
green
Over temperature
red
ENCLOSURE
Weight (kg)
1.8
Dimensions (hxwxd in mm)
65 x 120 x 260
STANDARDS
Emission
EN 50081-1
Immunity
EN 50082-1
Automotive Directive
2004/104/EC
Revision : Rev 04
Date : 18-05-2020
Table 1
(input AB) is less than 40 A,
please use this ATO fuse holder
Fuse AB Max. charge current
100 A
90 A
80 A
70 A
60 A
40 A
2 x 30 A 35 A
2 x 20 A 25 A
2 x 15 A
20 A
2 x 10 A
18 A
2 x 7.5 A
12 A
1

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln
1

Forum

victron-bms-12-200

Suche zurücksetzen

  • Hallo,
    muss der AB Port beim BMS 12/200 (nicht smart) verwendet werden, oder kann dieser frei bleiben?
    Freundliche Grüße,
    Harald Franz
    Eingereicht am 23-7-2024 23:39

    Antworten Frage melden

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Victron BMS 12-200 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info