20
One alarm LED
lights and the
second flashes.
The inverter is switched off due to
alarm activation by the lighted LED.
The flashing LED indicates that the
inverter was about to switch off due
to the related alarm.
Check this table for appropriate
measures in regard to this alarm
state.
The charger does
not operate.
The AC input voltage or frequency is
not within the range set.
Ensure that the AC input is between
185 VAC and 265 VAC, and that the
frequency is within the range set
(default setting 45-65 Hz).
Circuit breaker or fuse in the
AC-in input is open as a result of
overload.
Remove overload or short circuit on
AC-out-1 or AC-out-2, and reset
fuse/breaker.
The battery fuse has blown.
Replace the battery fuse.
The distortion or the AC input voltage is
too large (generally generator supply).
Turn the settings WeakAC and
dynamic current limiter on.
The charger does
not operate.
“Bulk” LED flashes
and
“Mains on” LED
illuminates.
MultiPlus is in “Bulk protection” mode
thus, the maximum bulk charging time
of 10 hours is exceeded.
Such a long charging time could
indicate a system error (e.g. a battery
cell short-circuit).
Check your batteries.
NOTE:
You can reset the error mode by
switching off and back on the
MultiPlus.
The standard MultiPlus factory setting
of the “Bulk protection” mode is
switched on. The “Bulk protection”
mode can be switched off with help of
VEConfigure only.
The battery is not
completely charged.
Charging current excessively high,
causing premature absorption phase.
Set the charging current to a level
between 0.1 and 0.2 times the battery
capacity.
Poor battery connection.
Check the battery connections.
The absorption voltage has been set to
an incorrect level (too low).
Set the absorption voltage to the
correct level.
The float voltage has been set to an
incorrect level (too low).
Set the float voltage to the correct
level.
The available charging time is too short
to fully charge the battery.
Select a longer charging time or
higher charging current.
The absorption time is too short. For
adaptive charging this can be caused
by an extremely high charging current
with respect to battery capacity, so that
bulk time is insufficient.
Reduce the charging current or select
the ‘fixed’ charging characteristics.
The battery is
overcharged.
The absorption voltage is set to an
incorrect level (too high).
Set the absorption voltage to the
correct level.
The float voltage is set to an incorrect
level (too high).
Set the float voltage to the correct
level.
Poor battery condition.
Replace the battery.
The battery temperature is too high
(due to poor ventilation, excessively
high environmental temperature, or
excessively high charging current).
Improve ventilation, install batteries
in a cooler environment, reduce the
charging current, and connect the
temperature sensor.
The charging
current drops to 0
as soon as the
absorption phase
initiates.
The battery is over-heated (>50°C)
Install the battery in a cooler
environment
Reduce the charging current
Check whether one of the
battery cells has an internal
short circuit
Defective battery temperature sensor
Disconnect the temperature sensor
plug in the MultiPlus. If charging
functions correctly after
approximately 1 minute, the
temperature sensor should be
replaced.
22

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Victron MultiPlus 48 3000 35-50 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info