785542
7
Zoom out
Zoom in
Vorherige Seite
1/138
Nächste Seite
5
EN NL FR DE FI SE Appendix
3.OPERATION
3.1 On/Off/Charger Only Switch
When switched to on, the product is fully functional. The inverter will come into operation and the LED inverter onwill light up.
An AC voltage connected to the AC interminal will be switched through to the AC outterminal, if within specifications. The inverter will
switch off, the mains onLED will light up and the charger commences charging. The bulk, absorptionor floatLEDs will light up,
depending on the charger mode.
If the voltage at the AC-interminal is rejected, the inverter will switch on.
When the switch is switched to charger only, only the battery charger of the Multi will operate (if mains voltage is present). In this mode
input voltage also is switched through to the AC outterminal.
NOTE: When only the charger function is required, ensure that the switch is switched to charger only. This prevents the inverter from
being switched on if the mains voltage is lost, thus preventing your batteries from running flat.
3.2 Remote control
Remote control is possible with either a switch or with a Multi Control panel.
The Multi Control panel has a simple rotary knob with which the maximum current of the AC input can be set: see PowerControl and
PowerAssist in Section 2.
3.3 Equalisation and forced absorption
3.3.1 Equalisation
Traction batteries require regular additional charging. In the equalisation mode, the MultiPlus-II will charge with increased voltage for
one hour (1 V above the absorption voltage for a 12 V battery, 2 V for a 24 V battery). The charging current is then limited to 1/4 of the
set value. The bulkand absorptionLEDs flash intermittently.
Equalisation mode supplies a higher charging voltage than most DC consuming
devices can cope with. These devices must be disconnected before additional
charging takes place.
3.3.2 Forced absorption
Under certain circumstances, it can be desirable to charge the battery for a fixed time at absorption voltage level. In Forced Absorption
mode, the MultiPlus-II will charge at the normal absorption voltage level during the set maximum absorption time. The absorption
LED lights.
3.3.3 Activating equalisation or forced absorption
The MultiPlus-II can be put into both these states from the remote panel as well as with the front panel switch, provided that all switches
(front, remote and panel) are set to onand no switches are set to charger only’.
In order to put the MultiPlus-II in this state, the procedure below should be followed.
If the switch is not in the required position after following this procedure, it can be switched over quickly once. This will not change the
charging state.
NOTE: Switching from onto charger onlyand back, as described below, must be done quickly. The switch must be toggled such that
the intermediate position is 'skipped', as it were. If the switch remains in the offposition even for a short time, the device may be turned
off. In that case, the procedure must be restarted at step 1. A certain degree of familiarisation is required when using the front switch on
the Compact in particular. When using the remote panel, this is less critical.
Procedure:
1. Check whether all switches (i.e. front switch, remote switch or remote panel switch if present) are in the onposition.
2. Activating equalisation or forced absorption is only meaningful if the normal charging cycle is completed (charger is in 'Float').
3. To activate:
a. Switch rapidly from onto charger onlyand leave the switch in this position for ½ to 2 seconds.
b. Switch rapidly back from charger onlyto onand leave the switch in this position for ½ to 2 seconds.
c. Switch once more rapidly from onto ‘charger onlyand leave the switch in this position.
4. On the MultiPlus-II (and, if connected, on the MultiControl panel) the three LEDs Bulk, Absorptionand Floatwill now flash 5 times.
5. Subsequently, the LEDs Bulk, Absorptionand Float will each light during 2 seconds.
a. If the switch is set to onwhile the BulkLED lights, the charger will switch to equalisation.
b. If the switch is set to onwhile the AbsorptionLED lights, the charger will switch to forced absorption.
c. If the switch is set to onafter the three LED sequence has finished, the charger will switch to Float’.
d. If the switch is has not been moved, the MultiPlus-II will remain in ‘charger only’ mode and switch to Float’.
7

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Victron MultiPlus II 48 3000 35-32 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info