785558
13
Zoom out
Zoom in
Vorherige Seite
1/192
Nächste Seite
11
EN NL FR DE ES SV IT Appendix
4.4 Connection options
4.4.1 Starter battery (connection terminal E, see appendix A)
The Quattro has a connection for charging a starter battery. Output current is limited to 4A.
(not available on 48V models)
4.4.2 Voltage sense (connection terminal E, see appendix A)
For compensating possible cable losses during charging, two sense wires can be connected with which the voltage direct on
the battery or on the positive and negative distribution points can be measured. Use at least wire with a cross-section of
0,75mm2.
During battery charging, the Quattro will compensate the voltage drop over the DC cables to a maximum of 1 Volt (i.e. 1V over
the positive connection and 1V over the negative connection). If the voltage drop threatens to become larger than 1V, the
charging current is limited in such a way that the voltage drop remains limited to 1V.
4.4.3 Temperature sensor (connection terminal E, see appendix A)
For temperature-compensated charging, the temperature sensor (supplied with the Quattro) can be connected. The sensor is
isolated and must be fitted to the negative terminal of the battery.
4.4.4 Remote control
The Quattro can be remotely controlled in two ways:
- With an external switch (connection terminal H, see appendix A). Operates only if the switch on the Quattro is set to “on”.
- With a remote control panel (connected to one of the two RJ48 sockets B, see appendix A). Operates only if the switch on the
Quattro is set to “on”.
Using the remote control panel, only the current limit for AC-in-2 can be set (in regard to PowerControl and PowerAssist).
The current limit for AC-in-1 can be set with DIP switches or by means of software.
Only one remote control can be connected, i.e. either a switch or a remote control panel.
4.4.5. Programmable relays (connection terminal I and E (K1 and K2), see appendix A
The Quattro is equipped with 3 programmable relays. The relay that controls terminal I is set as an alarm relay (default setting).
The relays can be programmed for all kinds of other applications, for example to start a generator (VEConfigure software
needed).
4.4.6 Auxiliary AC output (AC-out-2)
Besides the usual uninterruptable output (AC-out-1), a second output (AC-out-2) is available that disconnects its load in the
event of battery operation. Example: an electric boiler or air conditioner that is allowed to operate only if the genset is running or
shore power is available.
In case of battery operation, AC-out-2 is switched off immediately. After the AC supply has become available, AC-out-2 is
reconnected with a delay of 2 minutes, this allow a genset to stabilise prior to connecting a heavy load.
4.4.7 Connecting Quattro’s in parallel (see appendix C)
The Quattro can be connected in parallel with several identical devices. To this end, a connection is established between the
devices by means of standard RJ45 UTP cables. The system (one or more Quattro’s plus optional control panel) will require
subsequent configuration (see Section 5).
In the event of connecting Quattro units in parallel, the following requirements must be met:
- A maximum of 6 units connected in parallel.
- Only identical devices with the same power ratings may be connected in parallel.
- Battery capacity should be sufficient.
- The DC connection cables to the devices must be of equal length and cross-section.
- If a positive and a negative DC distribution point is used, the cross-section of the connection between the batteries and the
DC distribution point must at least equal the sum of the required cross-sections of the connections between the distribution
point and the Quattro units.
- Place the Quattro units close to each other, but allow at least 10 cm for ventilation purposes under, above and beside the
units.
- UTP cables must be connected directly from one unit to the other (and to the remote panel). Connection/splitter boxes are not
permitted.
- A battery-temperature sensor need only be connected to one unit in the system. If the temperature of several batteries is to be
measured, you can also connect the sensors of other Quattro units in the system (with a maximum of one sensor per Quattro).
Temperature compensation during battery charging responds to the sensor indicating the highest temperature.
- Voltage sensing must be connected to the master (see Section 5.5.1.4).
- Only one remote control means (panel or switch) can be connected to the system.
4.4.8 Three-phase configuration (see appendix C)
Quattro’s can also be used in 3-phase wye (Y) configuration. To this end, a connection between the devices is made by means
of standard RJ45 UTP cables (the same as for parallel operation). The system (Quattro’s plus an optional control panel) will
require subsequent configuration (see Section 5).
Pre-requisites: see Section 4.4.7.
Note: the Quattro is not suitable for 3-phase delta (Δ) configuration.
13

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Victron Quattro 24 5000 120-100 100 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info