813785
64
Zoom out
Zoom in
Vorherige Seite
1/72
Nächste Seite
64
Control strategy
The control strategy specifies in which operating
ranges the heat pump and/or external heat generator
operates.
These operating ranges also depend on the operating
mode set by your heating contractor.
Parallel operation
ABA
+
Fig. 16
ϑAOutside temperature
ALower temperature limit, value dependent on the
control strategy
BUpper temperature limit
The heat pump is switched on for room heating/
room cooling and DHW heating as required.
The external heat generator is switched on for cen-
tral heating and DHW heating as required.
When outside temperature is above the upper tem-
perature limit B:
Room heating/room cooling and DHW heating are
supplied only by the heat pump.
The external heat generator does not start.
When outside temperature is between the two tem-
perature limits:
For normal heat demand, only the heat pump is
switched on.
For increased heat demand, the external heat gen-
erator is switched on in addition to the heat pump.
The heat pump can be switched on for room cool-
ing.
When outside temperature is below the lower tem-
perature limit A:
The heat pump does not operate.
Room heating and DHW heating are supplied only
by the external heat generator.
Room cooling is switched off.
Alternative operation
AA
Fig. 17
ϑAOutside temperature
ATemperature limit, value dependent on the control
strategy
The heat pump is switched on for room heating/
room cooling and DHW heating as required.
The external heat generator is switched on for cen-
tral heating and DHW heating as required.
When the outside temperature is above temperature
limit A:
Room heating/room cooling and DHW heating are
supplied only by the heat pump.
The external heat generator does not start.
When the outside temperature is below temperature
limit A:
The heat pump does not operate.
Room heating and DHW heating are supplied only
by the external heat generator.
Room cooling is switched off.
The temperature limits of these operating ranges are
determined in the control strategy.
Ecological control strategy
The control unit specifies the temperature limit A
based on what will achieve the lowest CO2 emissions.
The heat pump control unit calculates the resulting
CO2 emissions on the basis of the primary energy fac-
tors for electricity and fossil fuels.
The primary energy factors are stored in the heat
pump control unit. During an update, the primary
energy factors are automatically updated.
Economical control strategy
The control unit specifies the temperature limit A
based on what will achieve the lowest running costs.
The heat pump control unit calculates the running
costs on the basis of the energy prices you have
entered for electricity and fossil fuels.
You can enter the energy prices via the ViCare app.
Appendix
Terminology (cont.)
6199646
64

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Viessmann VITOCAL 252-A wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Viessmann VITOCAL 252-A

Viessmann VITOCAL 252-A Bedienungsanleitung - Deutsch - 80 seiten

Viessmann VITOCAL 252-A Bedienungsanleitung - Holländisch - 76 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info