Manual_S5_Airplus_2015_04_20 Page 54 / 68
© Wodtke GmbH - Tübingen. All Rights and Changes Reserved.Printed 04/2015 Part No. 950 976
Fault code
Class 1
Cause of fault
Target values
Resolution of fault
TR =
Flue gas temperature
too low. Measurement point:
Combustion chamber.
Sensor NiCrNi
Image / case 1
Do not ignite! Empty pot
first. See to the right
Flue gas fan temperature TR
too low. There are often also unburned
pellets in the burner pot.
Case 1: False start; burner pot filled
with pellets, no flame. TR temperature
not reached:
Burner pot / unit not cleaned
false start
Negative pressure in installa-
tion room (resulting in flow re-
versal in the ignition) false
start (often associated with flue
gas escaping from the unit)
Ignition cartridge defective
false start
TR ≥ 150 °C
Query occurs 18
minutes after the
start signal for
the furnace for
the first time, and
is then monitored
continually.
Upon restart, the
query waits 18
minutes again.
Always clean / empty burner
pot before restarting. Atten-
tion: Never empty content of
burner pot into the storage
container risk of fire from
embers!
Troubleshooting: Inspect,
verify combustion air supply.
Negative pressure in the in-
stallation room of the furnace
due to exhaust hood, residen-
tial ventilation or pneumatic
conveyance systems is not
permitted and dangerous.
Also see country-specific reg-
ulations and separate tech-
nical information. Inspect igni-
tion cartridge. Only after-
wards, perform manual reset
via I/O button
Image / case 2
Do not ignite! Empty pot
first. See to the right
Case 2 cause: Shut-down in opera-
tion, because there aren't enough pel-
lets in the storage container or container
has run empty (there are only a few pel-
lets in the burner pot)
Remedy for case 2: refill pel-
lets, empty / clean burner pot.
Reset and restart.
TP =
Pellet chute temperature too
high
Measurement point: Pellet
chute
Measurement sensor: TP 1000
External error!
Caused for example by negative pres-
sure due to ventilation system or extrac-
tion hood. Or chimney draught much too
low with voltage failure (fan). Or pellets
with through-put/heating value that is
much too high.
TP < 200 °C
There is not a unit defect!
Allow unit to cool until TP is
below threshold.
Find and resolve exter-
nal cause. Only afterwards,
manual reset via I/O button
See above regarding nega-
tive pressure
ST =
safety temperature limiter STB
has triggered!
Measurement point of air units:
capillary sensor on storage
container radiation plate
STB measurement sensor ac-
cording to DIN 3440. Notice,
the STB is a mandatory, au-
tonomous safety component
with its own switch housing
and operates decoupled
from the control.
External error!
Unit temperature is too high. STB trig-
gered because temperature is too high
(safety function). Normally an external
cause, not a unit fault, because STB is
only triggered if the heat generated by
the unit is not withdrawn.
Causes: Overheating
T STB ≤ 95 °C
no query possi-
ble.
There is not a unit defect.
Find and resolve external
cause. Inspect convection
air inlets and outlets. Re-
duce heating output if the
room temperature is too
high.
Allow unit to cool until STB
is below threshold. Only af-
terwards, unlock the STB+
manual reset via I/O button
54

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Wodtke Easy.nrg S5 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Wodtke Easy.nrg S5

Wodtke Easy.nrg S5 Bedienungsanleitung - Deutsch - 68 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info