© Wodtke GmbH Tübingen. All rights reserved. Subject to change without notice. Month of issue 03/2011 Art. No. 950 325
Data Queries
Press “Menu“ key once. Use the “+” and “-“ keys to move through the menu.
Display
message
Menu level
Explanation Remarks
BM
001, 002... Currently installed software version Identifies the basic software installed on the main
circuit board (cf. computer operating system).
Z
ON / OFF Z ON = ignition on
Z OFF = ignition off Shows whether the “Zündung Z“ (ignition) output is live
(ON) or not (OFF).
S
... Feed screw interval in seconds Shows the current working time interval of the feed
screw in seconds; this determines pellet feed rate.
PE CAL Calibration routine for pellet throughput Start routine here. Observe Operating Manual! Permits
adjusting pellet throughput according to pellet type or
batch.
U
... Fan speed in % Shows the current voltage at the “fan” output in terms
of % of nominal voltage.
L
... Air flow rate at the air flow sensor in m3/h Shows the combustion air flow currently measured by
the air flow sensor (LM) in terms of m3/h.
TP
... Temperature at pellet chute in °C Shows the temperature currently measured by the TP
sensor at the pellet chute.
TL
... Temperature at air flow sensor in °C Shows the temperature of the combustion air currently
measured by the LM in the suction pipe.
TR
... Flue gas temperature in °C Shows the combustion temperature currently
measured by the TR sensor in the firebox.
TW
... Temperature at water heat exchanger in
°C Shows the water temperature currently measured by
the internal boiler sensor in the heat exchanger.
P
ON / OFF
Pump relay (make-contact relay)
P ON = pump on = 230 V or mains voltage
P OFF = pump off = 0 V
Shows whether the “Pumpe” (pump) output is live
(ON) or not (OFF).
R1
ON / OFF
Auxiliary relay 1 (make-contact relay)
R1 ON = 230 V or mains voltage
R1 OFF = 0 V
Functional message
ON = stove is running (though error may be present)
OFF = stove not in operation
R2
ON / OFF
Auxiliary relay 2 (make-contact relay)
R2 ON = 230 V or mains voltage
R2 OFF = 0 V
Collective error message
ON = no error
OFF = has produced an error shutdown / has been
switched off manually
R3
ON / OFF
Auxiliary relay 3 (make-contact relay)
R3 ON = 230 V or mains voltage
R3 OFF = 0 V
Error message from temp. sensor at pellet chute (TP)
ON = temperature at pellet chute (TP) too high
OFF = temperature at pellet chute (TP) ok
R4
ON / OFF
Auxiliary relay 4 (break-contact relay,
potential-free, max. load 2 A)
R4 ON = relay open
R4 OFF = relay closed
Functional message (via monitored potential-free
safety relay)
ON = stove is running (though error may be present)
OFF = stove not in operation
BW
... Operating hours since last servicing x 10 Example: BW 56 = 560 hours since last servicing.
BG
... Total operating hours x 100 Example: BG 56 = 5,600 total operating hours. This
counter cannot be reset.
PR
... Remaining pellet consumption (in tons)
until next cleaning is due
Examples: PR -0.9 = another 0.9 t of pellets can be
burnt before the next cleaning becomes due.
PR 0.2 = cleaning overdue since 0.2 t.
PW
Remaining pellet consumption (in tons)
until next servicing is due
Examples: PW -2.9 = another 2.9 t of pellets can be
burnt before the next servicing becomes due.
PW 0.2 = servicing overdue since 0.2 t.
PG
Total pellet consumption in tons Example: PG 66.5 = 66.5 t of pellets have been burnt
in total. Cannot be reset.
wodtke GmbH • Rittweg 55-57 • D-72070 Tübingen-Hirschau
Tel. +49 (0) 70 71 / 70 03 - 0 • Fax +49 (0) 70 71 / 70 03 - 50
info@wodtke.com • www.wodtke.com
Please appreciate that we will not be liable for changes following the printing of this documentation or for printing errors.
Kurzanleitung_S5_Ausgabe_2011_04_07_Englisch
4

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Wodtke Ivo.safe S5 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Wodtke Ivo.safe S5

Wodtke Ivo.safe S5 Bedienungsanleitung - Deutsch - 80 seiten

Wodtke Ivo.safe S5 Bedienungsanleitung - Französisch - 80 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info