Installation
6720813171 (2016/05)16
Install the gas valve connector 1" [1] (accessory).
Install the gas valve [2] onto the gas pipe. Use a gas valve with a
minimum diameter of 1".
Fig. 14 Making the gas connection
[1] Gas valve connector 1"
[2] Gas valve 1"
Connect the main gas pipe to the gas connection making sure it is not
under stress. Use a gas pipe of at least Ø 22 mm.
Make the gas connection according to the country-specific standards
and regulations.
Carry out gas leak test on gas connection using leak detection spray
and purged as described in IGE/UP/1b.
Installing the heating flow and return pipe
The central heating system should be installed in accordance with
BS 6798 and, in addition, for small bore and micro bore systems,
BS 5449 or EN 12823.
Connect the flow pipe with a flat rubber seal installed to the CHF
(CH boiler flow) connection [1] making sure it is not under stress.
Use a flow pipe with a minimum diameter of 1½".
Connect the return pipe with a flat rubber seal installed to the CHR
(CH boiler return) connection [2] making sure it is not under stress.
Use a return pipe with a minimum diameter of 1½".
Fig. 15 Connecting the boiler flow and return
[1] CH boiler flow
[2] CH boiler return
[3] Isolating valves
[4] Drain cock
[5] Gas valve
[6] Pressure relief valve
[7] Condensate trap
[8] Pump
[9] Non-return valve
[10] Dirt filter
8.2.4 Installing the differential pressure controller
In situations where there is no low loss header, installing a bypass with a
differential pressure controller would not be required.
If a low loss header is present, it may be required -depending on the
situation - to install a bypass with a differential pressure controller to the
secondary side of the low loss header. This serves to protect the
secondary pump against overheating as a result of insufficient flow.
8.2.5 Installing the isolating valves
Install a isolating valve for maintenance and repair purposes in both
the boiler flow and return circuits ( fig. 15, [3]). Use isolating
valves with a minimum diameter of 1½".
8.2.6 Installing the drain cock
Connect a drain cock in the return circuit ( fig. 15, [4]).
8.2.7 Installing a pressure relief valve
Install a 4-bar pressure relief valve ( fig. 15, [6]) with a minimum
passage of 22 mm in the flow circuit. Make sure that the pressure
relief valve is always installed between the boiler and the isolating
valve, so that the boiler will always be in contact with the pressure
relief valve, even if the isolating valves are closed.
8.2.8 Selecting and installing the pump
Select a pump according to the hydraulic boiler resistance specified
in table 5 or in the curve in fig. 122 on page 62.
When using the curve take the nominal required volume flow into
consideration according to table 3.
When selecting the pump, take the maximum volume flow of the
boiler according to table 4 into consideration.
When using plastic pipes, observe the supplier’s
instructions - especially those referring to
recommended jointing techniques and the notes relating
to the heating system water on page 6
NOTICE:
To prevent contamination in the heating system we
recommend you to integrate a dirt filter [10] in the
return pipe, near the boiler. In an old system it is a
requirement to install a dirt filter.
Install shut-off valves to enable filter cleaning
immediately upstream and downstream of the dirt
filter.
2
G1”
R1”
6 720 648 726-014.1TD
1
CAUTION: Damage to the installation.
The pressure in the heating system can become
excessively high.
Install a pressure relief valve.
10
3 3
6 720 648 726-015.1TD
7
4
1
6
3
5
3
8
9
2
16

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Worcester-Bosch GB162-80 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Worcester-Bosch GB162-80

Worcester-Bosch GB162-80 Installationsanweisung - Englisch - 12 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info