Malfunction or failure
17
Greenstar 2000 – 6 721 839 343 (2023/04)
System gassing
WARNING
If you suspect the heating system is gassing, you must exercise
caution when carrying out testing or remedial work as the gasses
produced can be flammable.
Do not vent air from radiators whilst the central heating is switched
on. Allow 30mins after venting the radiators before using the
central heating or hot water.
Whilst venting radiators, do not allow the pressure on the boiler to
drop below the point at which it is normally set.
If the system is to be drained, the boiler must be electrically isolated.
CAUTION
If system pressure is repeatedly increasing, even when the
appliance is not operating, you should first check that the filling link
is fully closed and confirm that it is not passing. If radiators are also
not heating to the top of the panels and repeatedly need venting, the
heating system may be suffering from gassing. This is an indication
that corrosion is taking place and requires the system being cleaned
and treated to BS7593.
This should be confirmed by taking water samples to check pH levels
and turbidity.
Failure to properly maintain the heating system may result in damage
to the system and appliance, and may affect the boiler warranty.
Table 8 System gassing flow chart
Is your system pressure constantly increasing even when the boiler is off for extended
periods of time?
NO YES
Does system pressure increase
when the boiler is on?
Have you confirmed that the filling link is not
stuck open/passing water in any way?
YES YES
NO NO Does the problem
persist?
Is your system pressure regularly
dropping (i.e. you constantly have to
top up your boilers pressure)
Does system pressure increase above
2.5bar or enter the high pressure red
zone (Max operating pressure) on the
pressure gauge/display?
Confirm the filling link is closed
and check that the Plate Heat
Exchanger is not cross leaking
YES NO
The boiler
is fine
Plate heat exchanger leaking?NO YES NO YES
The boiler
is fine
Does your Pressure
Relief Valve
regularly drip?
The boiler
is fine
Is the Expansion Vessel
pre-charged higher than
expected?
Replace Plate Heat
Exchanger
NO YES
Do the radiators have to be
regularly vented?
NO YES NO YES
Most likely a cross-leaking
component in the boiler.
Further investigation
required
Check the CH
system for leaks
Check/replace
Pressure Relief
Valve
Is the Expansion Vessel
pre-charge too low?
YES NO
NO YES
Corrosion is probably occurring within the heating
system which is causing system gassing.
The system should be cleaned and treated to comply with
BS 7593
Check Expansion Vessel is
sized correctly for the
system
Repressurise the
Expansion Vessel
17

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Worcester-Bosch Greenstar 2000 - GR2301iW wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info