ALARMS
6 720 802 172 (2012/06)22
14.7.24 SHORT CIRCUIT ON SENSOR E1X.TT.T5 ROOM
Function: The room temperature influence is set to 0, which means that
the room controller cannot affect the heating system any longer. The
alarm is activated when the sensor's value indicates a temperature
higher than +70 °C.
Reset condition: The value of the sensor indicates
< 70 °C.
Category: H.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has disappeared.
Contact your installer if the alarm remains active for more than three
hours or recurs often.
14.7.25 FAILURE ON SENSOR E2X.T8 HEAT TRANSFER FLUID OUT
Function: Activated when the sensor's value indicates a temperature
lower than 0 °C.
Reset condition: The value of the sensor indicates >0 °C.
Category: H.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has disappeared.
Contact your installer if the alarm remains active for more than three
hours or recurs often.
14.7.26 SHORT CIRCUIT ON SENSOR E2X.T8 HEAT TRANSFER
FLUID OUT
Function: Activated when the sensor's value indicates a temperature
higher than 110 °C.
Reset condition: The value of the sensor indicates
< 110 °C.
Category: H.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has disappeared.
Contact your installer if the alarm remains active for more than three
hours or recurs often.
14.7.27 FAILURE ON SENSOR E2X.T9 HEAT TRANSFER FLUID IN
Function: Activated when the sensor's value indicates a temperature
lower than 0 °C.
Reset condition: The value of the sensor indicates >0 °C.
Category: H.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has disappeared.
Contact your installer if the alarm remains active for more than three
hours or recurs often.
14.7.28 SHORT CIRCUIT ON SENSOR E2X.T9 HEAT TRANSFER
FLUID IN
Function: Activated when the sensor's value indicates a temperature
higher than 110 °C.
Reset condition: The value of the sensor indicates
< 110 °C.
Category: H.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has disappeared.
Contact your installer if the alarm remains active for more than three
hours or recurs often.
14.7.29 FAILURE ON SENSOR E2X.T10
Function: Activated when the sensor's resistance value indicates a
temperature lower than -20 °C.
Reset condition: The value of the sensor indicates
> -20 °C.
Category: H.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has disappeared.
Contact your installer if the alarm remains active for more than three
hours or recurs often.
14.7.30 SHORT CIRCUIT ON SENSOR E2X.T10
Function: Activated when the sensor indicates a temperature in excess
of 70 °C.
Reset requirement: The sensor value displayed < 70 °C.
Category: H.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has disappeared.
Contact your installer if the alarm remains active for more than three
hours or recurs often.
14.7.31 FAILURE ON SENSOR E2X.T11
Function: Activated when the sensor's value indicates a temperature
lower than -50 °C.
Reset condition: The value of the sensor indicates
> -50 °C.
Category: H.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has disappeared.
Contact your installer if the alarm remains active for more than three
hours or recurs often.
14.7.32 SHORT CIRCUIT ON SENSOR E2X.T11
Function: Activated when the sensor indicates a temperature in excess
of 70 °C.
Reset requirement: The sensor value displayed < 70 °C.
Category: H.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has disappeared.
Contact your installer if the alarm remains active for more than three
hours or recurs often.
14.8 WARNINGS
14.8.1 ELECTRIC ADDITIONAL HEAT SHUT DOWN DUE TO HIGH
TEMPERATURE E2X.T8
Function: The electric heater is turned off. The warning is activated in
additional heat mode if the outgoing temperature of the heat transfer
fluid exceeds the maximum value.
Reset condition: The warning is deactivated when the temperature
falls.
Category: K.
Alarm lamp: Yes.
Restart: Automatic once the alarm cause has disappeared.
Contact your installer if the warning recurs often.
14.8.2 HIGH TEMPERATURE DIFFERENCE HEAT TRANSFER FLUID
E2X
Function: The warning is activated when the temperature difference
between heat transfer fluid out and heat transfer fluid in becomes too
high.
Reset condition: The warning is deactivated on acknowledgement of
the warning display.
22

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Worcester Greenstore Ground Source wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info