9.9. Help in the event of errors
ATTENTION: Opening the casing and manipulating the electrical connections is EXTREMELY DANGEROUS!
The mains fuse must be switched off before the front cover is removed.
WARNING: Due to external connections on the boiler control panel, individual cables or components on the
PYROGAS VARINO condensing unit can still be live even when the mains fuse is switched off.
9.9.1. No error code in the display
Unit is cold, the PYROGAS VARINO condensing unit is not in operation, no error code is shown in the display.
Status display: First figure = 0
Meaning: The condensing unit has no heat requirement and therefore no start command.
Possible cause: Ygnis heating controller (if present):
The heating controller is set to summer operation or switched off.
The operating instructions of the heating controller provide information on the
individual functions and applications of the heating controller.
External control with heating controller:
- the external heating controller should be checked.
- The heating curve may be set too low
Further procedure: Check cause, unit will start automatically when required.
Status display: First figure = 8
Meaning: Gas pressure monitor input is open
Possible cause: - The gas pressure is inadequate
- The gas cock is closed
- External safety gas valve is defect.
- The external mechanical ventilation does not work or builds up too little
pressure.
Further procedure: Check cause, unit will start automatically when required.
Status display: First figure = A
Meaning: The condensing unit is switched off
Possible cause: Fault lamp "external faults" lights up:
- The neutralisation set connected to the boiler control panel is overfull (if
present),
- external safety devices connected to the boiler control panel (e.g. water
shortage fuse, minimum/maximum pressure monitor, or external STB’s) have
been triggered.
Further procedure: The cause is not related to the condensing unit. After remedy of the external
cause the unit will start again without actuating the RESET button. A 5 minute
ventilation period will precede the start.
Possible cause: Fault lamp "external faults" does not light up:
- The burner switch on the control panel is switched OFF
- The maximum temperature set on the temperature monitor has been exceeded.
Further procedure: Check cause, unit will start automatically when required.
Possible cause: Fault lamp "sealing control" is lit (only when a sealing control has been optionally
added to the gas block):
- The gas supply is closed
- A leak has been found at one of the two gas valves of the gas block.
Further procedure: After the cause has been checked, the fault message must be acknowledged
with the "sealing control" release key. If the device still does not start after
acknowledgement has been made several times, the customer service must be
informed.
28

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Ygnis Varino wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Ygnis Varino

Ygnis Varino Bedienungsanleitung und Installationsanweisung - Deutsch - 30 seiten

Ygnis Varino Bedienungsanleitung und Installationsanweisung - Holländisch - 30 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info