623347
52
Zoom out
Zoom in
Vorherige Seite
1/54
Nächste Seite
Roll-ZAS
http://www.zennio.com Technical Support: http://zennioenglish.zendesk.com
52
160, 161
1 Bit
O
C T R - -
DPT_Switch
0/1
-
-
[Ix] Probe Error
1=Error;0=No Error
162, 164
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
25.00
-
[Tx] Temperature Source 1
External Sensor Measure
163, 165
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
25.00
-
[Tx] Temperature Source 2
External Sensor Measure
166, 167 1 Byte I
C - - W -
DPT_HVACMode
1=Comfort. 2=Standby
3=Economy
4=Protection
-
-
[Tx] Special Mode 1-byte HVAC Mode
168, 172
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[Tx] Special Mode: comfort
0=Nothing; 1=Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
-
-
[Tx] Special Mode: comfort
0=Off; 1=On
169, 173
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[Tx] Special Mode: standby
0=Nothing; 1=Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
-
-
[Tx] Special Mode: standby
0=Off; 1=On
170, 174
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[Tx] Special Mode: economy
0=Nothing; 1=Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
-
-
[Tx] Special Mode: economy
0=Off; 1=On
171, 175
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[Tx] Special Mode: protection
0=Nothing; 1=Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
-
-
[Tx] Special Mode: protection
0=Off; 1=On
176, 177
1 Bit
I
C - - W -
DPT_Window_Door
0/1
-
-
[Tx] Window Status (input)
0=Closed; 1=Open
178, 179
1 Bit
I
C - - W -
DPT_Trigger
0/1
-
-
[Tx] Comfort Prolongation
0=Nothing; 1=Timed Comfort
180, 181 1 Byte O
C T R - -
DPT_HVACMode
1=Comfort. 2=Standby
3=Economy
4=Protection
- W
- W
[Tx] Special Mode Status 1-byte HVAC Mode
182, 183
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
-
-
[Tx] Setpoint
Thermostat setpoint input
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
-
-
[Tx] Basic Setpoint
Reference setpoint
184, 185
1 Bit
I
C - - W -
DPT_Step
0/1
-
-
[Tx] Setpoint Step
0=-0.5ºC; 1=+0.5ºC
186, 187
2 Bytes
I
C - - W -
DPT_Value_Tempd
-670760.00 - 670760.00
-
-
[Tx] Setpoint Offset
Float offset value
188, 189
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 - 670760.00
- W
- W
[Tx] Setpoint Status
Current setpoint
190, 191
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 - 670760.00
- W
- W
[Tx] Basic Setpoint Status
Current basic setpoint
192, 193
2 Bytes
O
C T R - -
DPT_Value_Tempd
-670760.00 - 670760.00
- W
- W
[Tx] Setpoint Offset Status
Current setpoint offset
194, 195
1 Bit
I
C - - W -
DPT_Reset
0/1
-
-
[Tx] Setpoint Reset
Reset setpoint to default
1 Bit
I
C - - W -
DPT_Reset
0/1
-
-
[Tx] Offset Reset
Reset offset
196, 197
1 Bit
I
C - - W -
DPT_Heat_Cool
0/1
-
-
[Tx] Mode
0 = Cool; 1 = Heat
198, 199
1 Bit
O
C T R - -
DPT_Heat_Cool
0/1
- W
-
[Tx] Mode Status
0 = Cool; 1 = Heat
200, 201
1 Bit
I
C - - W -
DPT_Switch
0/1
-
-
[Tx] On/Off
0=Off; 1=On
202, 203
1 Bit
O
C T R - -
DPT_Switch
0/1
- W
- W
[Tx] On/Off Status
0=Off; 1=On
204, 206
1 Bit
O
C T R - -
DPT_Switch
0/1
- W
- W
[Tx] Control Variable (Cool)
2-Point Control
1 Bit
O
C T R - -
DPT_Switch
0/1
- W
- W
[Tx] Control Variable (Cool)
PI Control (PWM)
205, 207
1 Bit
O
C T R - -
DPT_Switch
0/1
- W
- W
[Tx] Control Variable (Heat)
2-Point Control
1 Bit
O
C T R - -
DPT_Switch
0/1
- W
- W
[Tx] Control Variable (Heat)
PI Control (PWM)
208, 210
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
- W
- W
[Tx] Control Variable (Cool)
PI Control (Continuous)
209, 211
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
- W
- W
[Tx] Control Variable (Heat)
PI Control (Continuous)
212, 214
1 Bit
O
C T R - -
DPT_Switch
0/1
- W
- W
[Tx] Additional Cool
Temp >= (Setpoint+Band) => "1"
52

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Zennio Roll-ZAS Touch Controller wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Zennio Roll-ZAS Touch Controller

Zennio Roll-ZAS Touch Controller Bedienungsanleitung - Deutsch - 49 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info