CodesDescription of the faultSolution for the fault
E 25Internal Control Fault: CRC check error. Turn unit o and on to resume normal operation.
E 30Supply Sensor Shorted: A short circuit has been detected in the appliance supply
temperature sensor circuit
1. Check supply temperature sensor and wiring harness for a short circuit.
2. If necessary replace the sensor, or the wire harness.
3. After xing the problem, reset the appliance and resume normal operation.
E 31Supply Sensor Open: An open circuit has been detected in the appliance supply
temperature sensor circuit
1. Check supply temperature sensor, connectors and wiring harness for an open circuit.
2. If necessary replace the sensor, or the wire harness.
3. After xing the problem reset the appliance and resume normal operation.
E 32DHW Sensor Shorted: A short circuit has been detected in the DHW temperature
sensor circuit
1. Check DHW temperature sensor and wiring harness for a short circuit.
2. If necessary replace the sensor, or the wire harness.
3. After xing the problem reset the appliance and resume normal operation.
E 33DHW Sensor Open: An open circuit has been detected in the DHW temperature
sensor circuit
1. Check DHW temperature sensor, connectors and wiring harness for an open circuit.
2. If necessary replace the sensor, or the wire harness.
3. After xing the problem reset the appliance and resume normal operation.
E 34Low Voltage: Line voltage has fallen below an acceptable operating level.The appliance will automatically reset once line voltage returns to normal.
E 37Low Water: Water level has fallen below 0.7 bar.1. Increase pressure to normal range.
2. The appliance will automatically reset once water level returns to normal.
E 43Return Sensor Shorted: A short circuit has been detected in the appliance return
temperature sensor circuit.
1. Check return temperature sensor and wiring harness for a short circuit.
2. If necessary replace the sensor, or the wire harness.
3. After xing the problem, reset the appliance and resume normal operation.
E 44Return Sensor Open: An open circuit has been detected in the appliance return
temperature sensor circuit.
1. Check return temperature sensor, connectors and wiring harness for an open circuit.
2. If necessary replace the sensor, or the wire harness.
3. After xing the problem, reset the appliance and resume normal operation.
E 45Flue Sensor Shorted: A short circuit has been detected in the appliance ue tem-
perature sensor circuit
1. Check ue temperature sensor and wiring harness for a short circuit.
2. If necessary replace the sensor, or the wire harness.
3. After xing the problem reset the appliance and resume normal operation.
E 46Flue Sensor Open: An open circuit has been detected in the appliance ue tem-
perature sensor circuit.
1. Check ue temperature sensor, connectors and wiring harness for an open circuit.
2. If necessary replace the sensor, or the wire harness.
3. After xing the problem reset the appliance and resume normal operation.
E47Water pressure sensor error: Water pressure sensor is disconnected or broken
1. Check water pressure sensor, connectors and wiring harness.
2. If necessary replace the sensor, or the wire harness.
3. After xing the problem reset the appliance and resume normal operation.
E 76
Gas pressure switch open
1. Check both the static and the dynamic gas pressures.
2. Correct condition which caused the pressure switch to open
3. Appliance will automatically reset once the pressure switch is closed.
External Limit Open: An external automatic reset appliance limit has opened.1. Correct condition which caused limit to open.
2. Appliance will automatically reset once external limit closes
E 77High temperature mixing circuitCheck if the mixing valve functions correctly.
E 78Mix circuit sensor shorted
1. Check Mix circuit temp. sensor and wiring harness for a short circuit.
2. If necessary replace the sensor, or the wire harness.
3. After xing the problem reset the appliance and resume normal operation.
Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.
Art des Missbrauchs:
Forenregeln
Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:
Lesen Sie zuerst die Anleitung;
Schauen Sie nach, ob die Frage bereits gestellt wurde;
Stellen Sie die Frage so deutlich wie nur einigermaßen möglich;
Erwähnen Sie was Sie bereits versucht haben um das Problem zu lösen;
Ist Ihr Problem von einem Besucher gelöst dann lassen Sie ihn / sie wissen in diesem Forum;
Falls Sie reagieren möchten, so verwenden Sie bitte das Antworten- Formular;
Da ihre Frage für alle Besucher sichtbar ist, sollten Sie lieber keine persönliche Daten erwähnen.
Neu registrieren
Registrieren auf E - Mails für ACV Watermaster wenn:
neue Frage gestellt werden
neue Handbücher vorhanden sind
Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.
Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.
Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.
Ihre Frage wurde zu diesem Forum hinzugefügt
Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.