Operation and maintenance manual - EN
EN
www.atmos.cz EN-59
This method of pump controlling can be used for any ATMOS pellet boiler, and is therefore
recommended. AD02 or AD03 modules must be inserted and connected under the boiler hood
and the TK sensor must be installed before this function can be activated. After activation, S37,
S38, S39, S40 temperature parameters must be checked and configured.
n) S14 = 14….. Reserve function for direct control of solar heating pump from the burner regulation
(boiler terminal board). This function control solar pump when automatic sensor switching function
is activated (S15 = 3), where the boiler is connected with accumulation tank equipped with solar
exchanger and collectors. The system requires TV, TK, TS and solar sensors to be connected to the
TSV solar panel. This function never uses AD02 or AD03 modules.
After activation, S26, S27, S28, S29, S30, S31, S32, S33 temperature parameters must be checked
and configured.
This function is specially designed for boilers: D14P, P14, D15P, P15, D20P, P20, D21P, P21,
D25P and P25
CAUTION - the direct controlling function of solar heating from pellet burner cannot be
used for
DCxxSP(X)/(EP), CxxSP, ACxxSP
boilers and boilers with burner built into the
upper doors. This function also cannot be used when the pump is simultaneously controlled
in the boiler circuit from the burner regulation (TK sensor cannot be simultaneously in boiler
and accumulation tank)
o) S14 = 15….. Reserve function for the compressor control during the function for automatic
burner cleaning using compressed air. Power element designed for switching and powering the
compressor (e.g. contactor) must be connected between reserve output R2 and the compressor.
This function is connected with S6(14), S41, S42, S43, S44, S45, S46, S47 parameter, which must
be checked and configured.
p) S14 = 16….. Reserve function for controlling el.fan during the function for automatic burner
cleaning using compressed air. This function is connected with S6 (14), S41, S42, S43, S44, S45,
S46, S47 parameter, which must be checked and configured.
Special function for turning on reserve output R2 according to the temperature of a concrete sensor:
a) e.g. function: TS>… means that if the TS sensor temperature is higher then the set value in S52
parameter – Temperature C, reserve output R2 will be activated
b) e.g. function: TS<… means that if the TS sensor temperature is higher then the set value in
S52 parameter – Temperature C, reserve output R2 will be deactivated
c) e.g. function: TS, TV>… means that if the TS and TV sensor temperature is higher at the same
time then the set value in S52 parameter – Temperature C and S54 – Temperature D, reserve output
R2 will be activated (Temperature C = first position (TS), Temperature D = second position (Tv)).
d) e.g. function TS, TK<… means that if the TS and TK sensor temperature is higher at the same
time then the set value in S52 parameter – Temperature C and S54 – Temperature D, reserve output
R2 will be deactivated (Temperature C = first position (TS), Temperature D = second position
(Tk)).
59

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Atmos A25 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Atmos A25

Atmos A25 Bedienungsanleitung - Deutsch - 70 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info