• Parameter S64 - characterizes the temperature of flue gas inside the heat exchanger of the boiler.
It serves to diagnoses the absense of pellets in the boiler tank or shows low output of the boiler. It
is not temperature of flue gas. Function is only for DxxPX (PXxx) boilers, burner profile A25PX.
Do not change… (130 °C)
Parameter S65 - characterizes start up time of the burner in OPERATION mode during which has to
be reached minimal waste gas temperature in the heat exchanger of the boiler set by parameter S64.
If in this time the boiler does not reach temperature the display shows ALARM SETTINGS –
REFILL PELLETS. In such case check the set output in parameters T4 and T6 and increase it.
In case of low pellets level in the tank fill up the fuel. Function is only for DxxPX (PXxx) boilers,
burner profile A25PX. Do not change… (120 min)
Parameter S66 - characterizes run-out time of the burner in OPERATION mode during which the
burner stays in operation when waste gas temperature in the heat exchanger of the boiler descend
under the temperature characterized by the parameter S64.
After the time characterized by the paramater S66 is display ALARM PELLETS – REFILL
PELLETS. In this case check the pellet tank and fill up the fuel.
DxxPX (PXxx) boilers are designed that after fuel refill is neccesary only to turn off and on the
main swich on the boiler. So it is not neccesary fill up the pellets into the conveyor after showen
ALARM PELLETS – REFILL PELLETS.
Function is only for DxxPX (PXxx) boilers, burner profile A25PX. Do not change… (30 min)
• Parameter S67 - characterizes function of R5 reserve output similar with S6 and S14 parameters
with instaled AC07X-C additional module. Primary is this reserve used to control air pump for
pellet burner pneumatic ash cleaning system S67 = 15.
Function is only for DC40GSP and DC40SPT boilers
or burners equiped with additional module
AC07X-C
, burner profile
A45GSP (A45GSP pneu) and A45SP (A45SP pneu)
....... (0)
if:
a) S67 = 1… If the burner gets into any failure and weaned, the reserve relay will be switched
on and the reserve output will be under the current. Thanks to this you can start a spare source
of energy for heating of the building as e.g. a gas, electric or oil boiler.
b) S67 = 2… If the burner gets into any failure and weaned, the reserve relay will be switched
off and the reserve output will not be under the current. As a result, we can send a signal to an
electrically backed -up device (GSM, WiFi, ...), which sends information that the device has fallen
into a fault or is not under current. This is the opposite logic (to S6 = 1), which means that the
reserve is under current during normal operation.
c) S67 = 4… The reserve function as the reversed function of the output for the burner fan,
when the reserve output is off, is not under the current, whenever the burner fan runs. Always
activate this function when you want the boiler extraction fan in DC40GSP and DC40SPT boilers
to run simultaneously with the pellet burner.
For this function the AD08 module is situated under boiler control panel in DC40GSP boilers,
see wiring diagram.
For this function the AD03 module is situated under boiler control panel in DC40SPT boilers,
see wiring diagram.
49

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Atmos A45SPT wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info