3.13 TECHNICAL SPECIFICATION OF THE REGULATOR
Power supply 230V + 10%, 50Hz
Input (not including the ventilator and pumps) < 4VA
Range of measuring the boiler temperature –9 – 109 °C+ 1 °C
Range of measuring the flue gas temperature –30–500 °C+ 1 °C
Max. input of devices connected to the regulator 2A/230V
CAUTION: not to get injured by the electrical current, do not remove the cover of device
before disconnecting it from electricity mains!
4 TECHNICAL DESCRIPTION OF THE ATTACK DPX LAMBDA
4.1 REGULATION OF BURNING
The boiler output is regulated according to the flue gas temperature by the air inlets to the
particular oxygen value. The flue gas temperature for burning down is adjusted. If there is a lot of
fuel (totally full feeding chamber) and the boiler temperature achieves 90 °C (overheating), the
flue gas fan is stopped, flap for primary air is closed and flap for secondary air is open for 25 %.
When the boiler temperature decreases to less than 88.5 °C, the flap for secondary air is for 30
seconds open for 100 % (chimney cleaning) and the primary air flap is regulated according to the
requirement for the flue gas temperature.
Automatic boiler stop: After the fuel burns out, the boiler can be stopped automatically or by
setting the flue gas temperature (TAG) or by a setting the value for oxygen (optional function).
Boiler stop by setting the flue gas temperature: When the fuel burns out and the flue gas
temperature decreases to less than 25 % of the adjusted value, the boiler stops after 15 minutes.
This is recommended only when the big or wet wood logs are being used.
Stop by the oxygen value: If the boiler works for more than 45 minutes and the oxygen value
exceeds 14 % for more than 15 minutes, then the boiler stops. This should be a standard function,
when the boiler cooling by chimney is limited. Ignition with remaining coal is easier and there is
less smoke by heating up.
When the boiler stops, the flue gas fan is stopped, the primary air flap is closed, the secondary air
flap remains open for 25 % until the flue gas temperature decreases below 100 °C.
Automatic restart after the power shortage: After the power shortage, the secondary air flap is
open for 100°%for 30 seconds to let the chimney clean.
Overheating (boiler temperature above 90 °C):The secondary air flap remains open for at least
25 %.
After turning the boiler off (automatically or manually):The primary air flap V1 is closed (0°%),
the flue gas temperature is above 100 °C, the secondary air flap remains open for at least 25 %
and function of the automatic operation is inactive.
4.2 IGNITING AND REFILLING THE FUEL
Basic instructions:
Check the pressure (and level of water) in the heating system before igniting.
The fuel has to be prepared in the boiler.
Ignite the fuel (see the prescriptions for boiler operation) and the rest of fuel in the
feeding chamber
30

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für ATTACK DPX wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von ATTACK DPX

ATTACK DPX Zusatzinformation - Deutsch - 21 seiten

ATTACK DPX Bedienungsanleitung - Deutsch - 48 seiten

ATTACK DPX Zusatzinformation - Englisch - 21 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info