[A 99] Temperature of boiler overheating – defines the value of boiler temperature to activate
the alarm of the boiler overheating.
[Fd60]Duration of boiler stop by ignition and fuel shortage – this parameter defines the
maximum time between starting the controller by the START button and achieving the
controller´s operating mode (reaching the flue gas temperature of [
c
90]). If the temperature of
[
c
90] is not reached during the heating up, the fan is stopped and the alarm FUEL (fuel shortage)
is displayed.
[Fb30]Duration of boiler stop by flue shortage and burn-down– the fuel amount test is
activated in the operating mode, when the flue gas temperature decreases under the parameter
[
c
90] or (if the flue gas sensor is not connected) when the boiler temperature decreases under
the adjusted parameter [L 45]. If the temperature does not exceed the necessary limit during this
period, the controller displays FUEL alarm.
[Ar 0] The control of the additional output-regulator is equipped with an additional
multifunctional output compatible with the options listed below (it is necessary to use the
additional UM-1 module for this purpose):
[Ar 0] parameter – indicates start of the automatic boiler (e.g. gas or pellet boiler). When
the controller is started and the boiler generates heat, the automatic boiler is stopped.
Operation of the automatic boiler is blocked by the controller in the operating mode. The
automatic boiler is started by controller, when the fuel is burned down in the boiler and
the FUEL alarm is displayed.
[Ar 1] parameter – indicates that the additional multifunctional output will be used for
error messages like boiler sensor failure, overheating or fuel shortage.
[
c
240]Adjusted flue gas temperature – the controller will struggle to reach and to keep this
value. The flue gas temperature sensor is turned off, if this parameter is set to „- -“.
[
c
h5]Hysteresis of flue gas temperature – defines the difference for which must the flue gas
temperature decrease to increase the fan rotations.
[
c
t 5]Time constant of stabilization the flue gas temperature – defines the period of
adjusting the fan rotations during stabilization of the flue gas temperature. If the flue gas
temperature exceeds the value given by the parameter [
c
240], the controller starts to decrease
the fan rotations gradually, until the flue gas temperature decreases to the adjusted value. If the
flue gas temperature decreases to the value of flue gas temperature hysteresis, the controller
starts to increase the fan rotations gradually.
[
c
F10]Blower speed jump while stabilizing exhaust gas temperature – defines the change of
rotations to achieve the adjusted flue gas temperature.
[
c
90]Flue gas temperature by fuel shortage – the message „FUEL“ for fuel shortage is
displayed after the flue gas temperature decreases under this value.
3.8 TESTING THE REGULATOR OUTPUTS
It is possible to make a check to test the correct functionality of the regulator and devices
connected. The correct function of fan is tested by selecting the [outΠ] on display and holding
the „OK“ button. Test of the circuit pump is done by selecting the [outP]. Select the [outu] to
start the additional output and [outr] for multifunctional additional output.
28

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für ATTACK DPX wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von ATTACK DPX

ATTACK DPX Zusatzinformation - Deutsch - 21 seiten

ATTACK DPX Bedienungsanleitung - Deutsch - 48 seiten

ATTACK DPX Zusatzinformation - Englisch - 21 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info