4.5 Connecting additional components
Note
The complete accessories can load the operator with max.
100 mA.
4.6 Connecting external IMPULSE buttons* to start or stop
door travel cycles
One or several buttons with closer contacts (floating),
such as internal buttons or key switches, is/are connected
(then parallel) as follows (see fig. 9):
1) first contact to terminal 21 (impulse input).
2) second contact to terminal 20 (0 V).
4.7 Connecting indoor button IT3b (see figure 10)
An indoor button IT3 is connected as follows:
1) Contact + to terminal 21 (impulse input).
2) Contact – to terminal 20 (0 V).
4.7.1 Connecting external IMPULSE button to start or stop
door travel cycles (see figure 10.1)
4.7.2 Light button: switch on / off operator lightning (see
figure 10.2)
4.7.3 Button: switch on / off radio system (see figure 10.3)
4.8 Connecting a cutout switch or a wicket door contact
(must feature forced opening) to stop and/or
cut off the operator (STOP or emergency-OFF
circuit)
A cutout switch with opener contact (floating) is connected
as follows (see fig. 11):
1) Connect the floating opener contact to terminals 12
(STOP or emergency-OFF input) and 13.
2)Set DIP switch 1 (SCH1) to OFF.
Note
By opening the contact any possible travel cycles are
immediately halted and permanently prevented. The
operator lighting signals the impulse code 1x flashing and LED 4
flashes.
4.9 Connecting a photocell* to initiate a safety return up to
the "OPEN” end-of-travel position
A photocell (safety device) that has a floating opener
contact is connected as follows (see fig. 12):
1) Connect the floating opener contact to terminals 71
(safety input) and 20 (0 V).
2) Connect terminals 5 (approx. + 24 V) and 20 (0 V) to
the voltage supply.
3)Set DIP switch 2 (SCH1) and DIP switch 1 (SCH2) to
OFF.
Note
If during the closing cycle the photocell is interrupted, the
door reverses and travels to the "OPEN" end-of-travel
position. If the automatic timer is activated, the time is
reset, i.e. as soon as the photocell is clear again, the set
time phase restarts. The connection is only active during
the closing cycle. The operator lighting signals the impulse
code once 1x flashing and LED 4 flashes.
4.10 Connecting a 2-wire light barrier* to initiate a safety
return up to the "OPEN” end-of-travel position
A 2-wire light barrier is connected as follows (see figure
13):
1) Connect the contact RX or TX to terminal 71 (safety
input) and the contact 0V to terminal 20 (0 V).
2) Set DIP switch 2 (SCH1) to OFF and DIP switch
1 (SCH2) to ON
Note
If during the closing cycle the photocell is interrupted, the
door reverses and travels to the "OPEN" end-of-travel
position. If the automatic timer is activated, the time is
reset, i.e. as soon as the photocell is clear again, the set
time phase restarts. The connection is only active during
the closing cycle. The operator lighting signals the impulse
code once 1x flashing and LED 4 flashes.
4.11 Connecting an optical protection of closing borders
8,2k*
A protection of closing borders (safety device) with 8,2k
resistance is connected as follows (see figure 14):
1) Remove the connected 8,2k resistance
2) Connect the protection of closing borders to the
terminals 74 (safety input) and 20 (0 V)
3) Set DIP switch 2 (SCH2) to OFF.
Note
If the light barrier is activated during the closing of the door the
door reverses in position „open“. In case of automatic closing
the the opening time is set back – after leafing the light barrier
time starts to run out from the beginning.
The light barrier is only active during the closing of the door.
The operator lightning flashes 1x and LED 4 flashes.
4.12 Connecting an optical protection of closing borders*
A protection of closing borders (safety device)
optosensors (Fraba) is connected as follows
(see figure 15):
1) Remove the connected 8,2k resistance
2) Connect the protection of closing borders to the
terminals 77 (+12 V), 74 (safety input) and 20 (0 V)
3) Set DIP switch 2 (SCH2) to ON.
Note
The input is active during the closing cycle. During the closing
cycle door reverses and travels to the "OPEN" end-of-travel
position. The operator lighting signals the impulse
code once 1x flashing and LED 3 flashes.
4.13 Connecting a warning light* to the optional relay
A warning lamp with max. 230V~/300W can be
connected to the floating closing contact terminal 1 and
2 (KL1) of the optional relay (see figure 21). The
warning light is on during every door cycle and flashes
during the warning time of “automatic closing”. Set DIP
switch 6 (SCH2) to OFF.
4.14 Connecting an external lamp to the optional relay
An additional external lamp with max. 230V~/300W can
be connected to the floating closing contact terminal 1
and 2 (KL1) of the optional relay (see figure 22). The lamp
is switched parallel to the operator lighting. Set DIP switch
6 (SCH2) to ON.
4.15 Connecting a “door closed” display to the optional
relay
An external “door closed” display with max. 230V~/300W
can be connected to the floating closing contact terminal
1 and 2 (KL1) of the optional relay (see figure 23). The
optional relay is activated during the end-of-travel position
“door closed”. Set DIP switch 8 (SCH2) to ON.
* Accessory is not included in delivery!
42
42

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln
1

Forum

berner-ga201

Suche zurücksetzen

  • Hallo
    Habe einen Garagentorantrieb von Berner. GA201.
    Der Handsender ist verloren gegangen. Berner hat mir den BHS 120 und später den BHS121 zugeschickt. Beide funktionieren nicht. Kann mir da jemand weiterhelfen? Eingereicht am 25-11-2022 09:14

    Antworten Frage melden
  • Hallo, habe das Garagentor Berner GA 201 /V2.
    Nun habe ich einen neuen Handsender RCBE 868 gekauft und finde leider weder hier noch im Internet die Anleitung, wie der Handsender am Empfänger programmiert werden kann.
    Wäre über eine kurze Hilfestellung sehr dankbar.
    Grüße
    G. Maneth Eingereicht am 12-6-2019 21:00

    Antworten Frage melden

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Berner GA201 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info