Commissioning
Condens 7000 WP – 6721841195 (2022/01)
22
8 Commissioning
WARNING
Escaping gas.
After completing the work, check the tightness of all gas-carrying
components.
CAUTION
Flue gas spillage.
Check the tightness of all flue gas routing parts once the work is
complete.
Complete the commissioning report during the commissioning
procedure (§ 15.7, p. 50).
8.1 Commissioning the boiler
NOTICE
Risk of boiler damage due to unsuitable fill water.
Check the chloride content of the fill water, if the maximum heating
water temperature is set higher than 80 °C ( § 5.4, p. 12).
Check whether the fill water satisfies the water quality requirements
( § 5.3, p. 12).
The boiler starts as soon as the operating pressure exceeds 0.8 bar.
If the operating pressure is lower than 0.2 bar, the appliance no longer
goes into operation.
Open all radiator valves.
Check whether the service shut-off valves of the connection sets are
open.
Use an appropriate filling method in line with Water Regulations.
(
§ 2.11, p. 6).
Fill the heating system to a pressure of 2 bar and close the filling
valve.
Vent the radiators.
Fill the heating system again to a pressure of 2 bar.
Open the gas cock.
Venting the gas line.
Operate the appliance.
Start up the boiler.
8.2 Setting the parameters
Different parameters can be set in the settings menu so the
boiler can be adapted to the heating system.
Go through the parameters in the menu Settings ( § 9.4, p. 26).
Adjust the parameters if required.
Make a note of which parameters have been modified in the
commissioning report ( § 15.7, p. 50).
Setting Maintenance type
With a maintenance period of 2 years, normal operation is considered to
be a maximum burner runtime of 4000 hours (every 2 years). During
commissioning, the anticipated burner runtime must be estimated in
order to set the right Maintenance type. During the initial inspection or
maintenance the burner runtime can be read out via the service menu
and the burner runtime Maintenance type modified if required.
Open the menu Maintenance > Maintenance type.
Based on the operation, estimate whether the maximum burner
runtime of 4000 hours will be exceeded in 2 years.
If the maximum burner runtime of 4000 hours in 2 years is likely to be
exceeded:
Set Burner run time to 4000 hours.
If the maximum burner runtime is likely to be less than 4000 hours:
Set Boiler run time to 24 months.
-or-
Set Service date: 24 months after installation date.
Table 8 Maintenance interval parameters
Setting Min. boiler outp.
If the boiler is installed in a positive pressure cascade system, the
minimum load must be increased.
Open the menu Limit values > Min. boiler outp..
Increase the setting Min. boiler outp. ( table 9).
Table 9 Setting the Min. boiler outp. with positive pressure cascade
systems
Setting Maintenance
type
Burner run
time
Boiler run
time
Service date
Standard operation 4000 hours 24 months Date: 24
months after
installation
Factory Raised value with
positive pressure
cascade
Appliance type: [%] [%]
GC7000WP 50 28 36
GC7000WP 65 20 26
GC7000WP 85 24 28
GC7000WP 100 20 23
22

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Bosch Condens GC7000WP wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Bosch Condens GC7000WP

Bosch Condens GC7000WP Installationsanweisung - Deutsch - 60 seiten

Bosch Condens GC7000WP Bedienungsanleitung - Deutsch - 12 seiten

Bosch Condens GC7000WP Bedienungsanleitung - Englisch - 12 seiten

Bosch Condens GC7000WP Installationsanweisung - Holländisch - 56 seiten

Bosch Condens GC7000WP Bedienungsanleitung - Holländisch - 12 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info