Commissioning
23
Condens 7000 WP – 6721841195 (2022/01)
8.3 Setting options for air/gas ratio control valve
Different air/gas ratio control valves are used depending on the rating
of the boiler. The positions of the various test ports and adjusting
screws vary accordingly.
Overview of air/gas ratio control valve GC7000WP 50, GC7000WP
65
Fig. 30 Overview of test ports and adjusting screws ≤ 70 kW
[1] Adjusting screw CO2/O2
[2] Gas pre-charge pressure test port
[3] Gas/air ratio test port
[4] Gas/air ratio adjusting screw
Overview of air/gas ratio control valve GC7000WP 85, GC7000WP
100
Fig. 31 Overview of test ports and adjusting screws ≥ 85 kW
[1] Adjusting screw CO2/O2
[2] Gas pre-charge pressure test port
[3] Gas/air ratio test port
[4] Gas/air ratio adjusting screw
[5] Without function
8.4 Measuring the gas standing pressure (static)
The gas standing pressure must be stable to guarantee correct
operation of the boiler. The measurement is carried out when the boiler
is switched off.
Switch off the appliance.
Remove the front panel.
Open the gas standing pressure test port by turning the adjusting
screw through 2 revolutions ( § 8.3, p. 23).
Set the pressure gauge to “0”.
Connect the pressure gauge to the test port.
Measure the static gas standing pressure.
Make a note of the value in the commissioning report ( § 15.7,
p. 50).
Close the inlet pressure test port.
8.5 Measuring the gas working pressure (dynamic)
The gas working pressure must be stable to guarantee correct operation
of the boiler. The measurement is performed at full load.
As the measurement is taken at the air/gas ratio control valve and not the
gas valve, the permissible gas working pressure may be reduced due to
the pressure drop between the gas valve and air/gas ratio control valve.
Example: GC7000WP 100 to natural gas H, G20.
Permissible gas pre-pressure: min. 17 mbar – max. 25 mbar (
Tab. 24, p. 48).
Pressure drop between gas valve and air/gas ratio control valve is
2.7 mbar ( Tab. 10).
Permissible limit values on the air/gas ratio control valve:
Min. 17 mbar – 2.7 mbar = 14.3 mbar.
Max. 25 mbar – 2.7 mbar = 22.3 mbar.
Table 10 Pressure drop between gas valve and air/gas ratio control valve
Calculate the permissible minimum and maximum gas pre-pressure.
Switch off the appliance.
Remove the front panel.
Open the gas inlet pressure test port by turning the adjusting screw
through 2 revolutions ( § 8.3, S. 23).
Set the pressure gauge to“0”.
Connect the pressure gauge to the test port.
Make sure the heating system can release its heat.
Operate the appliance.
Open the menu Function check > Burner.
Start the Function check by setting the value to 100%.
Check whether the measured value lies within the calculated limit
values.
If the measured value lies outside the calculated limit values, do not
commission the boiler. The cause must be established and the fault
rectified. If this is not possible, shut off the gas supply to the system and
contact the gas supplier.
Make a note of the measured value [mBar] after 1 minute in the
commissioning report ( § 15.7, p. 50).
▶Deactivate Function check.
Close the working pressure test port.
0010034262-001
32 4 1
0010034263-001
32 4
5
1
Max. pressure drop for each gas type
[mbar]
Type G20 G25 / G25.3
GC7000WP 50 1.5 2.0
GC7000WP 65 2.5 2.8
GC7000WP 85 2.6 3.3
GC7000WP 100 2.7 3.7
23

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Bosch Condens GC7000WP wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Bosch Condens GC7000WP

Bosch Condens GC7000WP Installationsanweisung - Deutsch - 60 seiten

Bosch Condens GC7000WP Bedienungsanleitung - Deutsch - 12 seiten

Bosch Condens GC7000WP Bedienungsanleitung - Englisch - 12 seiten

Bosch Condens GC7000WP Installationsanweisung - Holländisch - 56 seiten

Bosch Condens GC7000WP Bedienungsanleitung - Holländisch - 12 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info