The gross collector area, collector version and climate zone number
must be set correctly in order to achieve maximum energy savings and to
display the correct value for the solar yield.
Menu itemAdjustment rangeFunction description
Start diff. ctrl. heat. back.6 ... 20 KIf the differential set here between the cylinder temperature and heating return is exceeded and all conditions for
switching on have been met, the cylinder is integrated in the heating return for central heating backup via the 3-way
valve.
Stop diff. ctrl. heat. back.3 ... 17 KIf the differential between the cylinder temperature and the heating return falls below the value set here, the
cylinder is bypassed via the 3-way valve for central heating backup.
Max. mixer temp. CH20 ... 60 ... 90 °CThe temperature set here is the maximum temperature permitted in the heating return when achieved via central
heating backup.
Mixer runtime CH10 ... 120 ... 600 sThe elapsed time set here determines how long it takes the 3-way valve or the 3-way mixer to switch from "Cylinder
fully integrated in heating return" to "Bypass for the cylinder", or vice versa.
Table 19
The solar yield displayed is a calculated estimate of the
yield. If the heat meter function (L) is active, measured
values are displayed.
Menu itemAdjustment rangeFunction description
Gross collector area 10 ... 500 m
2
This function allows you to set the area installed in collector array 1. The solar yield is only displayed if an area
>0m
2
is set.
Type collector array 1Flat-plate collUse of flat-plate collectors in collector array 1
Vacuum tube collector
Use of vacuum tube collectors in collector array 1
Gross collector area 20 ... 500 m
2
This function allows you to set the area installed in collector array 2. The solar yield is displayed if an area > 0 m
2
is set.
Type collector array 2Flat-plate collUse of flat-plate collectors in collector array 2
Vacuum tube collector
Use of vacuum tube collectors in collector array 2
Climate zone1 ... 90 ... 255Climate zone of the installation location according to the map ( Fig. 42, page 188).
▶Search for the location of the system on the climate zones map and set the climate zone number.
Min. DHW temp.OffDHW reheating via the heat appliance irrespective of the minimum DHW temperature
15 ... 45 ... 70 °C
The control system determines whether solar yield is available and whether the stored amount of heat is sufficient
to supply DHW. The control system then reduces the set DHW temperature to be produced by the heat appliance in
accordance with these two values. If there is sufficient solar yield, there is therefore no need to reheat the DHW
with the heat appliance. If the temperature set here is not reached, the DHW is reheated by the heat appliance.
Solar infl. heat. circ. 1 ... 4OffSolar influence switched off.
– 1 ... – 5 K
Influence of solar on the set room temperature: at a high value, the flow temperature of the heating curve is reduced
at a correspondingly greater rate in order to enable greater passive solar energy input through the building's
windows. At the same time this reduces a temperature overshoot in the building and increases the comfort level.
•Increase heating circuit solar influence (– 5 K = max. influence) if the heating circuit heats rooms that have
large south-facing windows.
•Do not increase heating circuit solar influence if the heating circuit heats rooms that have small areas of north-
facing windows.
Reset solar yieldYesResets the solar yield to zero.
No
Reset solar optimisationYesResets the solar optimisation calibration and restarts it. The settings for Solar yield/optimisation remain
unchanged.
No
Set temp. Vario-Match-F.OffRegulates to a constant temperature differential between collector and cylinder (Match-Flow).
35 ... 45 ... 60 °C
Match-Flow (only in combination with speed modulation) is used to quickly heat the top part of the cylinder to
45 °C, for example, in order to prevent the potable water being reheated by the heat source.
Glycol content0 ... 45 ... 50 %In order to obtain accurate readings from the heat meter, the glycol content of the heat transfer medium must be
Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.
Art des Missbrauchs:
Forenregeln
Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:
Lesen Sie zuerst die Anleitung;
Schauen Sie nach, ob die Frage bereits gestellt wurde;
Stellen Sie die Frage so deutlich wie nur einigermaßen möglich;
Erwähnen Sie was Sie bereits versucht haben um das Problem zu lösen;
Ist Ihr Problem von einem Besucher gelöst dann lassen Sie ihn / sie wissen in diesem Forum;
Falls Sie reagieren möchten, so verwenden Sie bitte das Antworten- Formular;
Da ihre Frage für alle Besucher sichtbar ist, sollten Sie lieber keine persönliche Daten erwähnen.
Neu registrieren
Registrieren auf E - Mails für Bosch MS 200 wenn:
neue Frage gestellt werden
neue Handbücher vorhanden sind
Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.
Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.
Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.
Ihre Frage wurde zu diesem Forum hinzugefügt
Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.