Commissioning | 35
6 720 815 257 (2014/10)MS 200
Transfer
Solar DHW
4.5.2 Start solar thermal system
Menu item Adjustment range Function description
Transfer start diff. 6 ... 10 ... 20 K If the differential set here between cylinder 1 and cylinder 3 is exceeded and all conditions for switching on have
been met, the transfer pump is on.
Transfer stop diff. 3 ... 5 ... 17 K If the differential between cylinder 1 and cylinder 3 falls below the value set here, the transfer pump is off.
Start diff. diff. ctrllr 6 ... 20 K If the differential between the measured temperature at the heat source (TS14) and the measured temperature at
the heat sink (TS15) is above the set value, the output signal is on (only with Temp differential controller (R)).
Stop diff. diff. ctrllr 3 ... 17 K If the differential between the measured temperature at the heat source (TS14) and the measured temperature at
the heat sink (TS15) is below the set value, the output signal is off (only with Temp differential controller (R)).
Max source t. diff ctrllr 13 ... 90 ... 120 °C If the temperature at the heat source exceeds the value set here, the temperature differential controller switches off
(only with Temp differential controller (R)).
Min. source temp. Diff ctrl 10 ... 20 ... 117 °C If the temperature at the heat source exceeds the value set here and all conditions for switching on have been met,
the temperature differential controller switches on (only with Temp differential controller (R)).
Max setbck temp diff ctrl 20 ... 60 ... 90 °C If the temperature at the heat sink exceeds the value set here, the temperature differential controller switches off
(only with Temp differential controller (R)).
Table 21
WARNING: Risk of scalding!
If DHW temperatures above 60 °C are set or thermal
disinfection is switched on, a mixing valve must be
installed.
Menu item Adjustment range Function description
DHW controller act. Boiler One DHW system is installed and is controlled by the heat appliance.
2 DHW systems are installed. One DHW system is controlled by the heat appliance. The 2nd DHW system is
controlled by an MM 100 module (coding switch set to 10).
Thermal disinfection, reheating and solar optimisation only have an effect on the DHW system that is controlled by
the heat appliance.
external module 1
One DHW system is installed and is controlled by an MM 100 module (coding switch set to 9).
2 DHW systems are installed. Each DHW system is controlled by an MM 100 module (coding switch set to 9/10).
Thermal disinfection, reheating and solar optimisation only have an effect on the DHW system that is controlled by
external module 1 (coding switch set to 9).
external module 2
2 DHW systems are installed. One DHW system is controlled by the heat appliance. The 2nd DHW system is
controlled by an MM 100 module (coding switch set to 10).
2 DHW systems are installed. Each DHW system is controlled by an MM 100 module (coding switch set to 9/10).
Thermal disinfection, reheating and solar optimisation only have an effect on the DHW system that is controlled by
external module 2 (coding switch set to 10).
Therm.dis./daily ht cyl1 Yes Switches thermal disinfection and daily heat-up of cylinder 1 on or off.
No
Therm.dis./daily ht cyl2 Yes Switches thermal disinfection and daily heat-up of cylinder 2 on or off.
No
Therm.dis./daily ht cyl3 Yes Switches thermal disinfection and daily heat-up of cylinder 3 on or off.
No
Daily heat start time 00:00 ... 02:00
... 23:45 h
Start time for daily heat-up. Daily heat-up ends after a maximum of 3 hours. Only available if the MS 200 module is
installed in a BUS system without a heat source (not possible with all user interfaces).
Daily heat temp. 60 ... 80 °C Daily heat-up ends once the set temperature is reached, or, if the temperature is not reached, after a maximum of
3 hours. Only available if the MS 200 module is installed in a BUS system without a heat source (not possible with all
user interfaces).
Table 22
Menu item Adjustment range Function description
Start solar thermal
system
Yes The solar system only starts up once this function has been enabled.
Before starting up the solar thermal system, you must:
Fill and vent the solar thermal system.
Check the parameters for the solar thermal system and, if necessary, adjust them to suit the installed system.
No
This function can be used to switch off the solar system for maintenance purposes.
Table 23
35

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Bosch MS 200 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info