697439
4
Zoom out
Zoom in
Vorherige Seite
1/12
Nächste Seite
4 | Product Information
Uni 3000 F6 720 812 901 (2014/10)
2 Product Information
2.1 Intended use
The oil/gas-fired Uni 3000 F floor-standing high efficiency boiler has
been designed for hot water heating systems, e. g. for apartment
buildings or industrial units.
The boiler is only approved for open flue operation.
Any oil or gas burner to EN 676 and EN 267 can be used if its operating
range matches the boiler specification.
Only burners that have been tested and approved for electromagnetic
compatibility (EMC) may be used.
Control units from the CFB 9xx controller series are used with these
boilers.
The quality of fill and top-up water must comply with the specifications
in the boiler operator's log supplied.
For further detail on correct use, Chapter 2.4, page 4.
2.2 Gas Supply
The gas supply must be installed and maintained by a Gas safe registered
installer with the necessary experience and ACS elements to complete
the works.
Please note that, depending on the region, approvals for the flue
system and condensate connection to the public sewage system may
be required. Before starting installation, notify the responsible
agencies (e. g. the responsible flue gas inspector) and the wastewater
agency.
2.3 EU Declaration of Conformity
The design and operation of this product conform to the applicable
European directives and, when necessary, supplementary national
requirements. Conformity has been demonstrated.
You can ask for a copy of the Declaration of Conformity for this product.
For this see the contact address on the back cover of these instructions.
2.4 Overview of possible fuels
The boiler must only be operated with the specified fuels. Only burners
that are suitable for the specified fuels may be used. Your heating
contractor has entered the required type of fuel in Table 4, Chapter 10,
page 10.
2.5 Data plate
The data plate is located on the rear side of the boiler.
There you will find information such as the serial number, output and
approval details.
2.6 Appliance description
The Uni 3000 F is a stationary floor-standing boiler with dual-flue
combustion to EN 303/ EN 14394 for use with oil and gas as fuel.
It is referred to in this manual as the floor-standing boiler or the boiler.
The boiler consists of the following main components:
The boiler shell transfers the heat generated by the burner to the
heating water.
Boiler casing and thermal insulation [2]. The boiler jacket and thermal
insulation reduce heat losses.
Control unit (accessory [1]). The control unit monitors and controls
all electrical components of the boiler.
Fig. 1 Uni 3000 F oil/gas floor-standing boiler up to 1200 kW
[1] Control unit
[2] Boiler jacket
[3] Base frame
[4] Burner door
Fuels
28-second oil
(Kerosene)
35-second oil
(Gas Oil)
LPG 3P (G31) Natural Gas I2H
(G20)
Combustion of
biogas/waste gas
(quality in line with
DVGW G262
1)
,
table 3
1) Proportion of sulphur and sulphur compounds in the gas up to a maximum of
1500 mg/m
3
(approx. 0.1 % by volume)
Proportion of chlorine and chlorine compounds in the gas up to a maximum of
50 mg/m
3
Proportion of fluoride and fluoride compounds in the gas up to a maximum of
25 mg/m
3
Comment: The boiler must only be operated with the specified fuels.
Select a burner intended for the indicated fuels. Bosch Commercial
and Industrial Heating can provide a burner matching service, in
addition to supplying a selection of burners.
Table 2 Fuels
Please quote these details if you have to contact the
manufacturer because of a problem with your system.
These details enable us to assist you specifically and
quickly.
The information on the type plate is binding and must be
observed!
6 720 806 032-01.1ITL
4
3
1
2
4

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Bosch Uni 3000 F wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Bosch Uni 3000 F

Bosch Uni 3000 F Installationsanweisung - Englisch - 40 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info