SSB 6720818454 (2016/02) US
Troubleshooting | 41
6.1.1 Lockout errors
If an error is a “Lockout” error, it is necessary to press “RESET” button (after eliminating the reason for the failure) to restart the boiler.
In the following table the “Lockout” errors are listed:
Error Int. nr. Description Checks Solutions
"Ignit Error" 1
Three unsuccessful ignition attempts in
a row
a- Check gas supply
pressure;
b- Check ignition spark
c- Correct amount of gas;
d-Check for120VAC at the
gas valve;
a- If the gas supply pressure is
incorrect, it must be adjusted to the
correct pressure;
b- If spark is not present check for
correct ignition electrode position;
c- If the combustion air pressure is
incorrect, inspect the vent system
and eliminate any obstructions;
d- If the voltage to the gas valve is
not 120Vac the power control board
must be replaced.
"Gv Relay Error" 2
Failure detected in the GV (gas valve)
Relay
a- Check the integrity of the
wire connections between
gas valve and control board.
a- If wires are damaged, replace
them
b- If wires are ok, replace the gas
valve or the power control board.
"Gv Relay Not Open" 3
Failure detected in the GV (gas valve)
Relay
a- Check the integrity of the
wire connections between
gas valve and control board.
a- If wires are damaged, replace
them;
b- If wires are ok, replace the gas
valve or the power control board.
"Gv Relay Not Close" 4
Failure detected in the GV (gas valve)
Relay
a- Check the integrity of the
wire connections between
gas valve and control board.
a- If wires are damaged, replace
them;
b- If wires are ok, replace the gas
valve or the power control board.
"Safety Relay Error" 5 Failure detected in the Safety Relay Replace the power control board
"Safety Relay Open" 6 Failure detected in the Safety Relay Replace the power control board
"Safety Relay Closed" 7 Failure detected in the Safety Relay Replace the power control board
"Blocking Too Long Error" 11
Control had a blocking error for more
than 20 hours in a row
Press RESET button to
display the Blocking error
description
Remove the cause of the Blocking
error
"Fan Error" 12 Fan MF deviation for more than 60 sec
a- Check for 120 Vac power
connection of the fan.
b- Check PWM connection of
the fan.
a- If no 120 VAC voltage is present,
replace the power control board.
b- If no PWM signal is present,
replace power control board.
c- Replace the fan
"Ram Error" 13 Internal software error Replace the power control board
"Wrong E2prom Signature" 14 Contents of E2prom is not up-to-date Replace the power control board
"X Ram Error" 15 Internal software error Replace the power control board
"E2Prom Error" 16 No communication with E2prom Replace the power control board
"E2Prom Error C" 17 Wrong safety parameters in E2prom Replace the power control board
"E2Prom Error Cal Table" 18 Wrong calibtration table parameters Replace the power control board
"State Error" 19 Internal software error Replace the power control board
"Rom Error" 20 Internal software error Replace the power control board
"Rom Error C" 21 Internal software error Replace the power control board
"Air Sw Not Open" 22 Air pressure switch not working
"15Ms Xrl Error" 23 Internal software error Replace the power control board
"Air Sw Not Closed" 24 Air pressure switch not working
“Max. Thermostat Lock Error” 25
The external overheat protection is
activated
a- Check the pump to verify
the ow circulation
b- Check if the valves on
hydraulic circuit are open
c- Check the high limit switch
d- To reset - see “Fig. 10”,
section 4.4.2
a- Change the pump or restart it
b- Open the valves on hydraulic
circuit
c- Change the high limit switch
"Stack Error" 26 Internal error Replace the power control board
"Flame Out Too Late Error" 27
Flame still present 10 sec. after closing
the gas valve
Replace the gas valve
"Flame Error 1" 28 Flame is detected before ignition Replace the gas valve
"20Ms Xrl Error" 29 Internal software error Replace the power control board
"41Ms Error" 30 Internal software error Replace the power control board
Tab. 18 Lockout codes
41

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Buderus SSB512 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Buderus SSB512

Buderus SSB512 Installationsanweisung - Französisch - 68 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info