SSB 6720818454 (2016/02) US
Troubleshooting | 43
Error Int. nr. Description Checks Solutions
“Overheat Error” 70 Supply temp exceed the limit
a- Check the pump to verify
the ow circulation
b- Check if the valves on
hydraulic circuit are open
c- Check the supply
temperature sensor
a- Change the pump or restart it
b- Open the valves on hydraulic
circuit
c- Verify that the temperature sensor
has the correct resistance values. If
values are incorrect sensor must be
replaced.
"T Supply Open" 72 Supply sensor open
a- Check the integrity of the
wire connections
b- Check the supply
temperature sensor
a- If the wiring is damaged, replace
it
b- Verify that the temperature
sensor has the correct resistance
values. If values are incorrect
sensor must be replaced.
"T Return Open" 73 Return sensor open
a- Check the integrity of the
wire connections
b- Check the return
temperature sensor
a- If the wiring is damaged, replace
it
b- Verify that the temperature
sensor has the correct resistance
values. If values are incorrect
sensor must be replaced.
"T Dhw Out Open" 76 DHW sensor open
a- Check the integrity of the
wire connections
b- Check the DHW
temperature sensor
a- If the wiring is damaged, replace
it
b- Verify that the temperature
sensor has the correct resistance
values. If values are incorrect
sensor must be replaced.
"T Supply Shorted" 80 Supply sensor shorted
a- Check the integrity of the
wire connections
b- Check the supply
temperature sensor
a- If the wiring is damaged, replace
it
b- Verify that the temperature
sensor has the correct resistance
values. If values are incorrect
sensor must be replaced.
"T Return Shorted" 81 Return sensor shorted
a- Check the integrity of the
wire connections
b- Check the return
temperature sensor
a- If the wiring is damaged, replace
it
b- Verify that the temperature
sensor has the correct resistance
values. If values are incorrect
sensor must be replaced.
"T Dhw Out Shorted" 84 DHW sensor shorted
a- Check the integrity of the
wire connections
b- Check the DHW
temperature sensor
a- If the wiring is damaged, replace
it
b- Verify that the temperature
sensor has the correct resistance
values. If values are incorrect
sensor must be replaced.
"T Flue Shorted" 86 Flue sensor shorted
a- Check the integrity of the
wire connections
b- Check the ue temperature
sensor
a- If the wiring is damaged, replace
it
b- Verify that the temperature
sensor has the correct resistance
values. If values are incorrect
sensor must be replaced.
"Reset Button Error" 87 Reset button error
Too many reset button
pushes in a 60 sec period
"Appliance Selection" 93 Appliance selection error Replace the power control board
"Gas Pressure Error" 107 Gas pressure too low or too high
"Flue Press Error" 108 Flue gas pressure error
a- Check for any obstruction
in the exhaust system
b- Check the condensate
discharge
a- Remove any obstructions from
the exhaust system
b- Remove any obstruction from
condensate discharge and verify if
the condensate can ow freely
Tab. 19 Blocking errors
43

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Buderus SSB512 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Buderus SSB512

Buderus SSB512 Installationsanweisung - Französisch - 68 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info