brickwork with vermiculite (e.g. micafil or similar) concrete.
Ensure that there are no air pockets. The recommended mix is
six volumes of vermiculite granules to one volume of Portland
cement thoroughly mixed together. Enough water should be
added so that no more than one or two drops of water are
released when a handful of the mixture is squeezed.
After filling with vermiculite flaunch the top of the flue
connector pipe to the chimney with lime mortar.
Make good the holes in the front and side of the chimney
breast making sure that they are completely airtight. A typical
installation is shown in Fig. 11.
In most installations it will be possible to sweep the chimney
through the appliance. If this is not possible then some
alternative means (such as a soot door), must be provided.
The free inset method of installation may be used instead of
infilling. Details are available on request.
THERMOSTAT
Before lighting the fire check the cold setting distance of the
thermostat.
With the control knob at the maximum setting the flap should
be 18 mm from the air inlet as shown in Fig. 12. To adjust the
distance slacken the locking nut and adjust as necessary. When
set correctly re-tighten the locking nut. Ensure that the flap
opens and closes freely as the knob is turned.
ASSEMBLY
Fit the side panels and hood onto the appliance. Instructions
for this are enclosed with the panel pack. Replace any internal
parts previously removed.
PRE LIGHTING CHECK
Before initial lighting check the following points:
1. The bottom grate bars must all be fitted and should move
freely and easily when the riddling mechanism is operated.
2. The plates round the sides and back of the grate must be in
position and sitting correctly.
3. The throat plate must be fitted in the roof of the appliance
- see Fig. 13.
COMMISSIONING
On completion of the installation and after allowing a suitable
period of time for the fire cement and mortar to dry out, the
fire should be lit and checked to ensure that smoke and fumes
are taken from the appliance up the chimney and emitted
safely. Also check all joints and seals.
The central heating pump should be adjusted to give the
correct water flow against the circuit resistance and the
system should be correctly balanced.
On completion of the installation and commissioning please
leave the operating instructions with the customer and advise
on the use of the appliance and any controls on the system.
FREESTANDING KIT
A freestanding kit is available. Details of dimensions and
outputs are available on request.
®
INSTALLATION INSTRUCTIONS charnwood
Throat Plate
Throat Plate
rests on the
top of the bracket
Fig. 13. Throat Plate Position
Fig. 12. Thermostat Setting
18mm
Thermostat Flap
Locking Nut
14

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Charnwood LA45 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info