68 Maintenance
6.8 Performingsoftwareandrmwareupdates
To update the control software or the driver board rmware, proceed as follows:
1. Set the On/Off switch on the front side of the steam humidier to the Off position, then switch off the
voltage supply to the steam humidier via the external disconnect switch (electrical isolator) and
secure switch in the off position to prevent it from inadvertent power up.
2. Unlock the door panel on the control compartment side of the steam humidier and remove it.
3. Swing control panel assembly open.
4. Carefully insert FAT32 formatted USB memory stick containing the software updates into the USB
port on the control board. Make sure that the maximum length of the memory stick does exceed 75
mm.
Note: in order to update the control software or the rmware of the driver board a USB stick with a
valid software update (the update les must be on the highest level outside of any folder) must be
connected to the USB port on the control board. Otherwise, an appropriate fault message appears
when starting the software update.
5. Close control panel assembly, then close the door panel of the control compartment and lock it with
the screw.
6. Remove the lock and tag from the external disconnect switch. Then, switch on external disconnect
switch to restore power to the humidier.
7. Set the On/Off switch on the front side of the steam humidier to the On position.
8. When the standard operating display appears, select the <Menu> button, then enter the password
(8808) to login.
9. Select "Administrator > Software Update tab", then select the desired update function:
select "Software Update" to update the control software,
select "Driver A.DB.A" update the rmware for the driver board of Module A
select "Driver B.DB.B" update the rmware for the driver board of Module B (on double unit or
large units with two steam cylinders),
select "Driver C.DB.A" update the rmware for the driver board of optional Condair RO-A reverse
osmosis system (only possible, if Condair RS is congured for the operation with a Condair RO-A
reverse osmosis system).
The update starts. A progress bar is shown in the display. If the update has completed the control
unit returns to the standard operating display.
CAUTION!
Do not interrupt a software or rmware update once it has started. Wait until updating is completed.
Corrupted control software or rmware can render the humidier unusable.
Note: If software update is accidentally interrupted, the humidier will not operate, but the software
update can be resumed by leaving the USB key inserted in the control board and power cycling
the unit. The integrated controller will detect the software was not properly installed, and restart
the update.
10. Repeat steps 1 to 3, then carefully remove the USB memory stick.
11. Close control panel assembly, then close the door panel of the control compartment and lock it with
the screw.
12. Repeat Step 6 and 7 to power up the humidier.
68

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Condair RS wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Andere Handbücher von Condair RS

Condair RS Installationsanweisung - Englisch - 80 seiten

Condair RS Bedienungsanleitung - Holländisch - 80 seiten

Condair RS Installationsanweisung - Holländisch - 76 seiten


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info