TDMA CONTROL 601/701:
50
Published 07/2007
Input
Menu Setting
Necessary Sensor Con-
nection
Function
Location and Sensor Description
Sensor
Choice
F1
Basic function
yes
Solar regulating
Absorber outflow: Collector sensor
F2
Additional func-
tion 1
dependant on
function choice
East-West regulating
Absorber outflow: Collector sensor 2
F3
Basic function
yes
Limiting the thermal
store temperature,
back up heating
Cooling
Sensor casing A (FHA) or
B (FHB):
Upper thermal store sensor
F4
Basic function
yes
Solar regulating
Sensor casing F (FHF): Lower thermal store sensor
F5
Basic function
yes
Heating regulating 1
Heating inflow: Inflow temperature sensor 1
F6
Additional func-
tion 4
dependant on
function choice
Heating regulating 2
Heating inflow: Inflow temperature sensor 2
F7
Additional func-
tion 2
dependant on
function choice
Yield measurement
(Solar ein- Begren-
zung)
Sensor casing in CON-SOLAR STATION
Yield sensor (Heat exchanger inflow)
F8
Additional func-
tion 2
dependant on
function choice
Yield measurement
Sensor casing in CON-SOLAR STATION
Yield sensor (Heat exchanger outflow)
F9
Optional functi-
on 1
dependant on
function choice
Twin thermal store
Swimming pool
Lower buffer store: second lower thermal store sensor
Swimming pool: Swimming pool sensor
F10
Optional functi-
on 2
dependant on
function choice
Solid fuel boiler
T-PRO
Solid fuel boiler: Solid fuel boiler sensor
T-PRO Sensor 1: Position dependant on use
F11
Optional functi-
on 2
dependant on
function choice
Solid fuel boiler
T-PRO
Sensor casing E (FHE): Solid fuel boiler thermal store
sensor
T-PRO Sensor 2: Position dependant on use
F12
Additional func-
tion 6
dependant on
function choice
Boiler regulator
Boiler: Boiler sensor
F13
Additional func-
tion 3
dependant on
function choice
Buffer logic
Sensor casing C (FHC): Upper buffer region sensor
F14
Additional func-
tion 3
dependant on
function choice
Buffer logic
Sensor casing D (FHD): Lower buffer region sensor
F15
Optional functi-
on 3
dependant on
function choice
Frost protection
Insolation measuring
T- PRO 2
Collector pipework (at the coldest point): Frost protec-
tion sensor
Near the collector, with the same orientation: Solar in-
solation meter
Position dependant on use
F16
Basic function
yes
Heating regulating
House North Wall: External temperature sensor
D1
Additional func-
tion 2
No
Flow volume measu-
ring
Solar return flow: Flow volume meter
D2
Basic function
No
Override/Party switch
Heating circuit 1
Living area: Override/Party switch
D3
Additional func-
tion 4
No
Override/Party switch
Heating circuit 2
Living area: Override/Party switch
D4
no function
D5
no function
D6
Basic function
No
Circulation and bath
function
13)
Bathroom: Button
Key
Basic function: always activated
Optional Function / Additional Function:can be activated as
required.
Dependant on function option: depending on the set
function the relevant sensor must be connected. If no function
is chosen there is no connection.
Sensor / Output choice: Enter the system dependant con-
nection.
50

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Consolar Control 601 wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info