642450
18
Zoom out
Zoom in
Vorherige Seite
1/28
Nächste Seite
Installation and operation manual
15
EUWA(*)5~24KBZW1
Packaged air-cooled water chillers
4PW61653-1 – 07.2010
How to consult and modify the user parameters
For an overview of the menu structure, refer "Menu overview" on
page 21.
1 In case of digital controller, press the A and B keys for
approximately 5 seconds until O is displayed.
In case of remote user interface, push S once.
2 Enter the correct password by using the C and D keys.
The password’s value is 22.
3 Press the B key to confirm the password and to enter the
menu, s-p is displayed.
4 Press the B key to consult the parameter settings (=s-p).
(l-p means consulting the parameter level, but this function is
not used).
The -/- parameter group is displayed.
5 Press the C or D key to select the required parameter
group.
6 Press the B key to enter the selected parameter group.
7 Press the C or D key to select the required parameter.
8 Press the B key to consult the selected parameter.
9 Press the C or D key to increase, respectively decrease
the setting. (Only valid for read/write parameters.)
10 Press the B key to confirm the modified setting.
OR
Press the A key to cancel the modified setting.
11 Press the A key to return to the parameter group.
12 Press 2 times the A key to return to the main display.
If during the procedure no buttons are pressed for 30 seconds, the
displayed parameter code or value will start flashing. After another
30 seconds without pressing any buttons, the controller automatically
returns to the main display without saving any modified parameter.
Defining the cooling temperature differential
Modify the r02 cooling differential parameter.
This is a direct parameter, refer to "How to consult and modify the
direct parameters" on page 12.
Tasks carried out using user parameters
Defining the measurement unit
Depending on the setting of user parameter /23 (measurement
unit), all temperature values are displayed in °C (=0) or in °F (=1).
This is a user parameter, refer to "How to consult and modify the user
parameters" on page 15.
Defining the time delay between pump and compressor
startup
User parameter c07 allows you to define the time delay between the
pump startup and the compressor startup.
This is a user parameter, refer to "How to consult and modify the user
parameters" on page 15.
Defining the time delay between unit and pump shutdown
User parameter c08 allows you to define the time delay between the
unit shutdown and the pump shutdown, more specifically the period
during which the pump will still be active after the unit has been shut
down.
This is a user parameter, refer to "How to consult and modify the user
parameters" on page 15.
Defining the timer threshold for maintenance warning
User parameter c14 allows you to define a timer threshold (running
hours of the compressor) after which the controller will generate a
maintenance warning or request.
This is a user parameter, refer to "How to consult and modify the user
parameters" on page 15.
NOTE
When user parameters are consulted, the direct
parameters are displayed as well.
for 1 compressor
for 2 compressors
°C
r01/
r21
r02
12 15
inlet water
temperature of
evaporator
ON
OFF
compressor
°C
r01/
r21
r02
12 13.5 15
inlet water
temperature of
evaporator
ON
OFF
ON
compressor
OFF
4PW61653-1_digital_EN.book Page 15 Thursday, August 26, 2010 1:49 PM
18

Brauchen Sie Hilfe? Stellen Sie Ihre Frage.

Forenregeln

Missbrauch melden von Frage und/oder Antwort

Libble nimmt den Missbrauch seiner Dienste sehr ernst. Wir setzen uns dafür ein, derartige Missbrauchsfälle gemäß den Gesetzen Ihres Heimatlandes zu behandeln. Wenn Sie eine Meldung übermitteln, überprüfen wir Ihre Informationen und ergreifen entsprechende Maßnahmen. Wir melden uns nur dann wieder bei Ihnen, wenn wir weitere Einzelheiten wissen müssen oder weitere Informationen für Sie haben.

Art des Missbrauchs:

Zum Beispiel antisemitische Inhalte, rassistische Inhalte oder Material, das zu einer Gewalttat führen könnte.

Beispielsweise eine Kreditkartennummer, persönliche Identifikationsnummer oder unveröffentlichte Privatadresse. Beachten Sie, dass E-Mail-Adressen und der vollständige Name nicht als private Informationen angesehen werden.

Forenregeln

Um zu sinnvolle Fragen zu kommen halten Sie sich bitte an folgende Spielregeln:

Neu registrieren

Registrieren auf E - Mails für Daikin EUWA water chillers wenn:


Sie erhalten eine E-Mail, um sich für eine oder beide Optionen anzumelden.


Das Handbuch wird per E-Mail gesendet. Überprüfen Sie ihre E-Mail.

Wenn Sie innerhalb von 15 Minuten keine E-Mail mit dem Handbuch erhalten haben, kann es sein, dass Sie eine falsche E-Mail-Adresse eingegeben haben oder dass Ihr ISP eine maximale Größe eingestellt hat, um E-Mails zu erhalten, die kleiner als die Größe des Handbuchs sind.

Ihre Frage wurde zu diesem Forum hinzugefügt

Möchten Sie eine E-Mail erhalten, wenn neue Antworten und Fragen veröffentlicht werden? Geben Sie bitte Ihre Email-Adresse ein.



Info